6.8 15-** Drive Information
6.8.1 15-0* Operating Data
15-00 Operating hours
Range: Function:
0 h* [0 - 2147483647 h] View how many hours the unit has
run. The value is saved when the unit
is turned off.
15-01 Running Hours
Range: Function:
0 h* [0 - 2147483647
h]
View how many hours the filter has
run. Reset the counter in 15-07 Reset
Running Hours Counter. The value is
saved when the unit is turned off.
15-03 Power Up's
Range: Function:
0* [0 - 2147483647 ] View the number of times the unit has
been powered up.
15-04 Over Temp's
Range: Function:
0* [0 - 65535 ] View the number of unit temperature faults
that have occurred.
15-05 Over Volt's
Range: Function:
0* [0 - 65535 ] View the number of unit overvoltages that
have occurred.
15-07 Reset Running Hours Counter
Option: Function:
[0] * Do not
reset
[1] Reset
counter
Select [1] Reset and press [OK] to reset the
running hours counter to zero (see
parameter 15-01 Running Hours). This
parameter cannot be selected via the serial
port, RS485.
Select [0] Do not reset if no reset of the
running hours counter is desired.
6.8.2 15-1* Data Log Settings
The data log enables continuous logging of up to 4 data
sources (15-10 Logging Source) at individual rates
(parameter 15-11 Logging Interval). A trigger event
(15-12 Trigger Event) and window (15-14 Samples Before
Trigger) are used to start and stop the logging
conditionally.
15-10 Logging Source
Array [4]
Option: Function:
Select which variables are to be
logged.
[0] * None
[1600] Control Word
[1603] Status Word
[1630] DC Link Voltage
[1634] Heatsink Temp.
[1635] Inverter Thermal
[1660] Digital Input
[1666] Digital Output [bin]
[1690] Alarm Word
[1692] Warning Word
[1694] Ext. Status Word
15-11 Logging Interval
Array [4]
Range: Function:
Size related* [ 0.000 - 0.000 ] Enter the interval in ms between
each sampling of the variables to
be logged.
15-12 Trigger Event
Select the trigger event. When the trigger event occurs, a
window is applied to freeze the log. The log then retains a
specified percentage of samples before the occurrence of the
trigger event (parameter 15-14 Samples Before Trigger).
Option: Function:
[0] * False
[1] True
[2] Running
[6] Current limit
[16] Thermal warning
[19] Warning
[20] Alarm (trip)
[21] Alarm (trip lock)
[33] Digital input DI18
[34] Digital input DI19
[35] Digital input DI27
[36] Digital input DI29
15-13 Logging Mode
Option: Function:
[0] * Log always
Select [0] Log always for continuous
logging.
[1] Log once on
trigger
Select [1] Log once on trigger to
conditionally start and stop logging using
15-12 Trigger Event and 15-14 Samples Before
Trigger.