14-22 Operation Mode
Option: Function:
130BA097.12
FC 302
FC 301
FC 301 &
FC 302
1312 18 37322719 29 33 20
5039 42 5453 55
191812 13 203327 32
Illustration 6.8 Terminal Connections
[2] Initiali-
sation
Select [2] Initialisation to reset all parameter
values to default settings, except for
parameter 15-03 Power Up's,
parameter 15-04 Over Temp's, and
parameter 15-05 Over Volt's. The unit resets
during the next power-up.
Parameter 14-22 Operation Mode also reverts to
the default setting [0] Normal operation.
[3] Boot
mode
14-29 Service Code
Range: Function:
0* [-2147483647 - 2147483647] For internal service only.
14-50 RFI Filter
Option: Function:
[0] Off
Select [0] Off only if the unit is fed by an isolated
mains source (IT mains).
In this mode, the internal RFI filter capacitors between
chassis and the mains RFI filter circuit are cut-out to
reduce the ground capacity currents.
[1] * On
Select [1] On to ensure that the unit complies with
EMC standards.
14-54 Bus Partner
Range: Function:
1* [0 - 126 ]
Applications and Basic Prog... Operating Instructions
MG90V302 Danfoss A/S © 09/2014 All rights reserved. 51
6 6

Table of Contents

Other manuals for Danfoss VLT AAF006

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AAF006 and is the answer not in the manual?

Danfoss VLT AAF006 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AAF006
CategoryWater Filtration Systems
LanguageEnglish