6.6 8-** General Settings
6.6.1 8-0* General Settings
8-01 Control Site
Option: Function:
The setting in this parameter overrides
the settings in 8-50 Coasting Select to
8-56 Preset Reference Select.
[0] Digital and
ctrl.word
Control by using both digital input and
control word.
[1] Digital only Control by using digital inputs only.
[2] Controlword only Control by using control word only.
8-02 Control Word Source
This parameter cannot be adjusted while the motor is running.
Select the source of the control word: One of 2 serial interfaces
or 4 installed options. During initial power-up, the unit automat-
ically sets this parameter to [3] Option Aif it detects a valid
Fieldbus option installed in slot A. If the option is removed, the
unit detects a change in the configuration, sets
parameter 8-02 Control Word Source back to default setting [1] FC
RS485, and the unit then trips. If an option is installed after initial
power-up, the setting of parameter 8-02 Control Word Source does
not change but the unit trips and displays: Alarm 67 Option
Changed.
When retrofitting a bus option into a unit that did not have a
bus option installed to begin with, move the control to bus
based. This is done for safety reasons to avoid an accidental
change.
Option:
Function:
[0] None
[1] FC RS485
[2] FC USB
[3] Option A
[4] Option B
[5] Option C0
[6] Option C1
[30] External Can
8-03 Control Word Timeout Time
Range: Function:
1 s* [ 0.1 -
18000 s]
Enter the maximum time expected to pass
between the reception of 2 consecutive
telegrams. If this time is exceeded, it indicates
that the telegram communication has stopped.
The function selected in 8-04 Control Word
Timeout Function is then carried out. A valid
control word triggers the time-out counter.
8-04 Control Word Timeout Function
Select the time-out function. The time-out function activates
when the control word fails to be updated within the time
period specified in parameter 8-03 Control Word Timeout Time.
Option: Function:
[0] * Off Resumes control via serial bus (fieldbus or
standard) using the most recent control
word.
[2] Stop Stops with auto restart when communi-
cation resumes.
[5] Stop and trip Stops, then resets the unit in order to
restart: via the fieldbus, via [Reset] on the
LCP or via a digital input.
[7] Select setup 1 Changes the set-up upon reestablishment of
communication following a control word
time-out. If communication resumes causing
the time-out situation to disappear,
parameter 8-05 End-of-Timeout Function
defines whether to resume the set-up used
before the time-out or to retain the set-up
endorsed by the time-out function.
[8] Select setup 2
See [7] Select setup 1
[9] Select setup 3
See [7] Select setup 1
[10] Select setup 4
See [7] Select setup 1
NOTICE
The following configuration is required to change the
set-up after a time-out:
Set parameter 0-10 Active Set-up to [9] Multi set-up and
select the relevant link in parameter 0-12 This Set-up
Linked to.
8-05 End-of-Timeout Function
Option: Function:
Select the action after receiving a valid control
word following a time-out. This parameter is
active only when 8-04 Control Timeout
Function is set to [Set-up 1-4].
[0] Hold set-up
Retains the set-up selected in 8-04 Control
Timeout Function and displays a warning, until
8-06 Reset Control Timeout toggles. Then the
unit resumes its original set-up.
[1] * Resume
set-up
Resumes the set-up active before the time-
out.
8-06 Reset Control Word Timeout
This parameter is active only when [0] Hold set-up has been
selected in parameter 8-05 End-of-Timeout Function.
Option: Function:
[0] * Do not reset
Retains the set-up specified in 8-04 Control
Word Timeout Function, following a control
word time-out.
[1] Do reset Returns the unit to the original set-up
following a control word time-out. The unit
Applications and Basic Prog... Operating Instructions
48 Danfoss A/S © 09/2014 All rights reserved. MG90V302
66

Table of Contents

Other manuals for Danfoss VLT AAF006

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AAF006 and is the answer not in the manual?

Danfoss VLT AAF006 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AAF006
CategoryWater Filtration Systems
LanguageEnglish