8.3 Active Filter Warning and Alarm Definitions
NOTICE
After a manual reset pressing [Reset], press [Auto On] or [Hand On] to restart the unit.
If an alarm cannot be reset, the reason may be that its cause has not been rectified, or the alarm is trip-locked (see also
Table 8.1).
Alarms that are trip-locked offer additional protection, meaning that the mains supply must be switched off before the
alarm can be reset. After being switched back on, the unit is no longer blocked and may be reset as described in
chapter 8.2.2 Alarm Trip once the cause has been rectified.
Alarms that are not trip-locked can also be reset using the automatic reset function in 14-20 Reset Mode. Automatic wake-up
is possible during this type of reset.
If a warning and alarm is marked against a code in Table 8.1, either a warning occurs before an alarm, or the display for a
given fault (warning or alarm) is configurable.
Number Description Warning Alarm/Trip Alarm/Trip Lock Parameter Reference
1 10 Volts low X
2 Live zero error (X) (X) 6-01
4 Mains phase loss X
5 DC link voltage high X
6 DC link voltage low X
7 DC over voltage X X
8 DC under voltage X X
13 Over current X X X
14 Earth fault X X X
15 Hardware mismatch X X
16 Short circuit X X
17 Control word timeout (X) (X) 8-04
23 Internal fan fault X
24 External fan fault X 14-53
29 Heatsink temp X X X
33 Inrush fault X X
34 Fieldbus fault X X
35 Option fault X X
38 Internal fault
39 Heatsink sensor X X
40 Overload of digital output terminal 27 (X) 5-00, 5-01
41 Overload of digital output terminal 29 (X) 5-00, 5-02
46 Pwr. card supply X X
47 24 V supply low X X X
48 1.8 V supply low X X
65 Control board over-temperature X X X
66 Heat sink temperature low X
67 Option configuration has changed X
68 Safe torque off activated X
69 Pwr. card temp X X
70 Illegal FC configuration X
72 Dangerous failure X
73 Safe torque off auto restart
76 Power unit setup X
Maintenance, Diagnostics an... Operating Instructions
76 Danfoss A/S © 09/2014 All rights reserved. MG90V302
88

Table of Contents

Other manuals for Danfoss VLT AAF006

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AAF006 and is the answer not in the manual?

Danfoss VLT AAF006 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AAF006
CategoryWater Filtration Systems
LanguageEnglish