6.3 Description of Parameters
6.3.1 Main Menu
The main menu includes all available parameters in the
VLT
®
Active Filter. All parameters are grouped by name
indicating the function of the parameter group. All
parameters are listed by name and number in this manual.
6.4 0-** Operation/Display
Parameters in this group are related to the fundamental
functions of the active filter, function of the LCP keys, and
configuration of the LCP display.
6.4.1
0-0* Basic Settings
0-01 Language
Option: Function:
Defines the language to be used in the
display. The filter can be delivered with 4
different language packages. English and
German are included in all packages.
English cannot be erased or manipulated.
[0] * English Part of Language packages 1 - 4
[1] Deutsch Part of Language packages 1 - 4
[2] Francais Part of Language package 1
[3] Dansk Part of Language package 1
[4] Spanish Part of Language package 1
[5] Italiano Part of Language package 1
[6] Svenska Part of Language package 1
[7] Nederlands Part of Language package 1
[10] Chinese Part of Language package 2
[20] Suomi Part of Language package 1
[22] English US Part of Language package 4
[27] Greek Part of Language package 4
[28] Bras.port Part of Language package 4
[36] Slovenian Part of Language package 3
[39] Korean Part of Language package 2
[40] Japanese Part of Language package 2
[41] Turkish Part of Language package 4
[42] Trad.Chinese Part of Language package 2
[43] Bulgarian Part of Language package 3
[44] Srpski Part of Language package 3
[45] Romanian Part of Language package 3
0-01 Language
Option: Function:
[46] Magyar Part of Language package 3
[47] Czech Part of Language package 3
[48] Polski Part of Language package 4
[49] Russian Part of Language package 3
[50] Thai Part of Language package 2
[51] Bahasa
Indonesia
Part of Language package 2
[52] Hrvatski
0-04 Operating State at Power-up (Hand)
Option: Function:
Selects the operating mode upon
reconnection of the filter to mains voltage
after power down in Hand (local) operation
mode.
[0] Resume Restarts the filter maintaining the same start/
stop settings (applied by [HAND ON/OFF]) as
before the filter was powered down.
[1] * Forced stop Restarts the filter with a saved local reference,
after mains voltage reappears and after
pressing [HAND ON].
6.4.2 0-1* Set-up Operations
Define and control the individual parameter set-ups.
The active filter has 4 parameter set-ups that can be
programmed independently of one another, making it
flexible.
The active set-up (the set-up in which the active filter is
currently operating) can be selected in
parameter 0-10 Active Set-up and is displayed on the LCP.
Using multi set-up, it is possible to switch between set-ups
with the active filter running or stopped, via digital input
or serial communication commands. If it is necessary to
change set-ups while running, ensure that
parameter 0-12 This Set-up Linked to is programmed as
required. Using parameter 0-11 Edit Set-up, it is possible to
edit parameters within any of the set-ups while continuing
the active filter operation in its active set-up, which can be
a different set-up than the one being edited.
Use parameter 0-51 Set-up Copy to copy parameter settings
between the set-ups enabling faster commissioning if
similar parameter settings are required in different set-ups.
Applications and Basic Prog...
Operating Instructions
MG90V302 Danfoss A/S © 09/2014 All rights reserved. 41