6.12 Parameter Lists
6.12.1 Default Settings
Changes during operation:
True means that the parameter can be changed while the active filter is in operation, and False means that the unit must be
stopped before a change can be made.
4-Set-up:
All set-up: The parameter can be set individually in each of the 4 set-ups, (1 single parameter can have 4 different data
values).
1 set-up: Data value is the same in all set-ups.
SR:
Size-related.
N/A:
No default value available.
Conversion index:
This number refers to a conversion figure used when writing or reading with an active filter.
Conv.
index
100 75 74 70 67 6 5 4 3 2 1 0 -1 -2 -3 -4 -5 -6
Conv.
factor
1 3600000 3600 60 1/60 1000000 100000 10000 1000 100 10 1 0.1 0.01 0.001 0.0001 0.00001 0.000001
Table 6.11 Conversion Index
Data type Description Type
2 Integer 8 Int8
3 Integer 16 Int16
4 Integer 32 Int32
5 Unsigned 8 Uint8
6 Unsigned 16 Uint16
7 Unsigned 32 Uint32
9 Visible string VisStr
33 Normalised value 2 bytes N2
35 Bit sequence of 16 boolean variables V2
54 Time difference without date TimD
Table 6.12 Data Type and Description