Mains Supply 3 x 380 - 480 VAC - Normal overload 110% for 1 minute
Frequency converter
Typical Shaft Output [kW]
PK37
0.37
PK55
0.55
PK75
0.75
P1K1
1.1
P1K5
1.5
P2K2
2.2
P3K0
3
P4K0
4
P5K5
5.5
P7K5
7.5
Typical Shaft Output [HP] at 460 V 0.5 0.75 1.0 1.5 2.0 2.9 4.0 5.3 7.5 10
IP 20 / NEMA Chassis A2 A2 A2 A2 A2 A2 A2 A2 A3 A3
IP 21 / NEMA 1
IP 55 / NEMA 12 A5 A5 A5 A5 A5 A5 A5 A5 A5 A5
IP 66
A5 A5 A5 A5 A5 A5 A5 A5 AA A5
Output current
Continuous
(3 x 380-440 V) [A]
1.3 1.8 2.4 3 4.1 5.6 7.2 10 13 16
Intermittent
(3 x 380-440 V) [A]
1.43 1.98 2.64 3.3 4.5 6.2 7.9 11 14.3 17.6
Continuous
(3 x 441-480 V) [A]
1.2 1.6 2.1 2.7 3.4 4.8 6.3 8.2
11 14.5
Intermittent
(3 x 441-480 V) [A]
1.32 1.76 2.31 3.0 3.7 5.3 6.9 9.0 12.1 15.4
Continuous kVA
(400 V AC) [kVA]
0.9 1.3 1.7 2.1 2.8 3.9 5.0 6.9
9.0 11.0
Continuous kVA
(460 V AC) [kVA]
0.9 1.3 1.7 2.4 2.7 3.8 5.0 6.5 8.8 11.6
Max. cable size:
(mains, motor, brake)
[[mm
2
/ AWG]
2)
4/10
Max. input current
Continuous
(3 x 380-440 V ) [A]
1.2 1.6 2.2 2.7 3.7 5.0 6.5 9.0 11.7 14.4
Intermittent
(3 x 380-440 V ) [A]
1.32 1.76 2.42 3.0 4.1 5.5 7.2 9.9
12.9 15.8
Continuous
(3 x 441-480 V) [A]
1.0 1.4 1.9 2.7 3.1 4.3 5.7 7.4 9.9 13.0
Intermittent
(3 x 441-480 V) [A]
1.1 1.54 2.09 3.0 3.4 4.7 6.3 8.1
10.9 14.3
Max. pre-fuses
1)
[A]
10 10 10 10 10 20 20 20 30 30
Environment
Estimated power loss
at rated max. load [W]
4)
35 42 46 58 62 88 116 124 187 255
Weight enclosure IP20 [kg] 4.7 4.7 4.8 4.8 4.9 4.9 4.9 4.9
6.6 6.6
Weight enclosure IP 21 [kg]
Weight enclosure IP 55 [kg] 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5
14.2 14.2
Weight enclosure IP 66 [kg] 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 14.2 14.2
Efficiency
3)
0.93 0.95 0.96 0.96 0.97 0.97 0.97 0.97 0.97 0.97
10.1.4. Mains Supply 3 x 380 - 480 VAC
10. Specifications
VLT
®
AQUA Drive
Operating Instructions
152
MG.20.M5.02 - VLT
®
is a registered Danfoss trademark
10

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals