[2] Logic AND Activates Start command via the fieldbus/serial communication
port, AND additionally via one of the digital inputs.
[3]
*
Logic OR Activates Start command via the fieldbus/serial communication
port OR via one of the digital inputs.
Select control of the frequency converter start function via the
terminals (digital input) and/or via the fieldbus.
NB!
This parameter is active only when
par. 8-01 Control Site
is set to [0]
Digital and
control word
.
8-54 Reversing Select
Option: Function:
[0]
*
Digital input
[1] Bus Activates Reverse command via the serial communication port
or fieldbus option.
[2] Logic AND Activates Reverse command via the fieldbus/serial communica-
tion port, AND additionally via one of the digital inputs.
[3] Logic OR Activates Reverse command via the fieldbus/serial communica-
tion port OR via one of the digital inputs.
Select control of the frequency converter reverse function via
the terminals (digital input) and/or via the fieldbus.
NB!
This parameter is active only when
par. 8-01 Control Site
is set to [0]
Digital and
control word
.
8-55 Set-up Select
Option: Function:
[0] Digital input
[1] Bus Activates the set-up selection via the serial communication port
or fieldbus option.
[2] Logic AND Activates the set-up selection via the fieldbus/serial communi-
cation port, AND additionally via one of the digital inputs.
[3]
*
Logic OR Activate the set-up selection via the fieldbus/serial communica-
tion port OR via one of the digital inputs.
Select control of the frequency converter set-up selection via
the terminals (digital input) and/or via the fieldbus.
NB!
This parameter is active only when
par. 8-01 Control Site
is set to [0]
Digital and
control word
.
VLT
®
AQUA Drive Programming Guide 2. Parameter Description
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
113