EasyManuals Logo

Danfoss vlt aqua Programming Guide

Danfoss vlt aqua
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #247 background imageLoading...
Page #247 background image
26-15 Terminal X42/1 High Ref./feedb. Value
Range: Function:
100.000
Unit
*
[Par. 26-14 -
1000000.000]
Enter the analog input scaling value that corresponds to the high
voltage value set in par 26-11.
26-16 Terminal X42/1 Filter Time Constant
Range: Function:
0.001 s
*
[0.001 - 10.000 s] Enter the time constant. This is a first-order digital low pass filter
time constant for suppressing noise in terminal X42/1. A high
time constant value improves dampening but also increases the
time delay through the filter. This parameter cannot be adjusted
while the motor is running.
26-17 Terminal X42/1 Live Zero
Option: Function:
[0] Disabled
[1] Enabled This parameter makes it possible to enable the Live Zero mon-
itoring. E.g. where the analog input is a part of the frequency
converter control, rather than being used as part of a decentral
I/O system, such as a Building Management System.
26-20 Terminal X42/3 Low Voltage
Range: Function:
0.07 V
*
[0.00 - par. 26-21] Enter the low voltage value. This analog input scaling value
should correspond to the low reference/feedback value set in
par 26-24.
26-21 Terminal X42/3 High Voltage
Range: Function:
10.0 V
*
[Par. 26-20 - 10.0 V] Enter the high voltage value. This analog input scaling value
should correspond to the high reference/feedback value set in
par 26-25.
26-24 Terminal X42/3 Low Ref./feedb. Value
Range: Function:
0.000
Unit
*
[-100000.000 - par.
26-25]
Enter the analog input scaling value that corresponds to the low
voltage value set in par 26-20.
VLT
®
AQUA Drive Programming Guide 2. Parameter Description
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
247
2

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals