EasyManuals Logo

Danfoss vlt aqua Programming Guide

Danfoss vlt aqua
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
[3] Set-up 3
[4] Set-up 4
0-13 Readout: Linked Set-ups
Array [5]
0
*
[0 - 255] View a list of all the set-ups linked by means of par. 0-12
This
Set-up Linked to
. The parameter has one index for each pa-
rameter set-up. The parameter value displayed for each index
represents which setups are linked to that parameter setup.
Index
LCP value
0 {0}
1 {1,2}
2 {1,2}
3{3}
4 {4}
Table 2.1: Example: Set-up 1 and Set-up 2 are linked
0-14 Readout: Prog. Set-ups / Channel
Range: Function:
AAA.AA
A.AAA
*
[0 - FFF.FFF.FFF] View the setting of par. 0-11
Edit Set-up
for each of the four
different communication channels. When the number is dis-
played in hex, as it is in the LCP, each number represents one
channel.
Numbers 1-4 represent a set-up number; ‘F’ means factory set-
ting; and ‘A’ means active set-up. The channels are, from right
to left: LCP, FC-bus, USB, HPFB1.5.
Example: The number AAAAAA21h means that the FC bus se-
lected Set-up 2 in par. 0-11, the LCP selected Set-up 1 and all
others used the active set-up.
2.2.4. 0-2* LCP Display
Define the variables displayed in the Graphical Local Control Panel.
NB!
Please refer to parameters 0-37, 0-38 and 0-39 for information on how to write
display texts
0-20 Display Line 1.1 Small
Option: Function:
Select a variable for display in line 1, left position.
[0] None No display value selected
[37] Display Text 1 Present control word
2. Parameter Description VLT
®
AQUA Drive Programming Guide
30
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
2

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals