[3] Set-up 3
[4] Set-up 4
0-13 Readout: Linked Set-ups
Array [5]
0
*
[0 - 255] View a list of all the set-ups linked by means of par. 0-12
This
Set-up Linked to
. The parameter has one index for each pa-
rameter set-up. The parameter value displayed for each index
represents which setups are linked to that parameter setup.
Index
LCP value
0 {0}
1 {1,2}
2 {1,2}
3{3}
4 {4}
Table 2.1: Example: Set-up 1 and Set-up 2 are linked
0-14 Readout: Prog. Set-ups / Channel
Range: Function:
AAA.AA
A.AAA
*
[0 - FFF.FFF.FFF] View the setting of par. 0-11
Edit Set-up
for each of the four
different communication channels. When the number is dis-
played in hex, as it is in the LCP, each number represents one
channel.
Numbers 1-4 represent a set-up number; ‘F’ means factory set-
ting; and ‘A’ means active set-up. The channels are, from right
to left: LCP, FC-bus, USB, HPFB1.5.
Example: The number AAAAAA21h means that the FC bus se-
lected Set-up 2 in par. 0-11, the LCP selected Set-up 1 and all
others used the active set-up.
2.2.4. 0-2* LCP Display
Define the variables displayed in the Graphical Local Control Panel.
NB!
Please refer to parameters 0-37, 0-38 and 0-39 for information on how to write
display texts
0-20 Display Line 1.1 Small
Option: Function:
Select a variable for display in line 1, left position.
[0] None No display value selected
[37] Display Text 1 Present control word
2. Parameter Description VLT
®
AQUA Drive Programming Guide
30
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
2