0-43 [Reset] Key on LCP
Option: Function:
[0] Disabled No function
[1]
*
Enabled [Reset] Key is enabled
[2] Password Avoid unauthorized resetting. If par. 0-43 is included in the
Quick Menu, then define the password in par. 0-65
Quick Menu
Password
. Otherwise define the password in par. 0-60 Main
Menu Password.
2.2.7. 0-5* Copy / Save
Copy parameter settings between set-ups and to/from the LCP.
0-50 LCP Copy
Option: Function:
[0]
*
No copy No function
[1] All to LCP Copies all parameters in all set-ups from the frequency convert-
er memory to the LCP memory. For service purposes it is rec-
ommended to copy all parameters to the LCP after commission-
ing.
[2] All from LCP Copies all parameters in all set-ups from the LCP memory to the
frequency converter memory.
[3] Size indep. from LCP Copies only the parameters that are independent of the motor
size. The latter selection can be used to programme several fre-
quency converters with the same function without disturbing
motor data which are already set.
This parameter cannot be adjusted while the motor is running.
0-51 Set-up Copy
Option: Function:
[0]
*
No copy No function
[1] Copy to set-up 1 Copies all parameters in the present edit set-up (defined in par.
0-11
Edit Set-up
) to Set-up 1.
[2] Copy to set-up 2 Copies all parameters in the present edit set-up (defined in par.
0-11
Edit Set-up
) to Set-up 2.
[3] Copy to set-up 3 Copies all parameters in the present edit set-up (defined in par.
0-11
Edit Set-up
) to Set-up 3.
[4] Copy to set-up 4 Copies all parameters in the present edit set-up (defined in par.
0-11
Edit Set-up
) to Set-up 4.
[9] Copy to all Copies the parameters in the present set-up over to each of the
set-ups 1 to 4.
2. Parameter Description VLT
®
AQUA Drive Programming Guide
40
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
2

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals