5.12.4 12-3* EtherNet/IP
Parameter 12-30 Warning Parameter
Table 628: Parameter 12-30 Warning Parameter
12-30 Warning Parameter
Default value: 0
Parameter type: Range, 0 - 2147483647
Setup: All setups
Conversion index: 0
Data type: Uint32
Change during operation: True
This parameter is read-only. It shows the EthetNet/IP-specific 16-bit status word.
Table 629: 16-Bit Status Word, EtherNet/IP
Bit
Description
0
Owned
1
Not used
2
Configured
3
Not used
4
Not used
5
Not used
6
Not used
7
Not used
8
Minor recoverable fault
9
Minor unrecoverable fault
10
Major recoverable fault
11
Major unrecoverable fault
12
Not used
13
Not used
14
Not used
15
Not used
Parameter 12-31 Net Reference
Table 630: Parameter 12-31 Net Reference
12-31 Net Reference
Default value: [0] Off
Parameter type: Option
Setup: 2 setups
Conversion index: –
Data type: Uint8
Change during operation: True
Shows the reference source in instance 21/71.
Option
Name
Description
[0]*
Off
[1]
On
AU275636650261en-000101 / 130R0334 | 361Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 Series and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals