Parameter 42-15 Feedback Filter
Table 1377: Parameter 42-15 Feedback Filter
Parameter type: Range, 0.01 - 200 Hz
Change during operation: False
Frequency of the feedback filter. The default value is 200 Hz (off) if the encoder resolution is higher than 150 PPR. A filter value of
200 Hz is selected, meaning the filter is off. The use of filters depends on the given encoder resolution, gear ratio, and feedback
type.
Parameter 42-16 Mounting Type
Table 1378: Parameter 42-16 Mounting Type
Default value: [0] Motor shaft mounted
Change during operation: False
Parameter 42-18 Zero Speed Timer
Table 1379: Parameter 42-18 Zero Speed Timer
Parameter type: Range, 0 - 10000 h
Change during operation: False
Time period where the option is allowed to be below 120 RPM when SLS is active before STO is activated.
5.31.3 42-2* Safe Input
Parameter 42-20 Safe Function
Table 1380: Parameter 42-20 Safe Function
Default value: Size related
Change during operation: False
Enable any of the safety options or disable safety option for the digital safe inputs.
AU275636650261en-000101 / 130R0334670 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide