Parameter 14-38 Field Weakening Controller Gain
Table 730: Parameter 14-38 Field Weakening Controller Gain
14-38 Field Weakening Controller Gain
Default value: 20%
Parameter type: Range, 10 - 100%
Setup: All setups
Conversion index: 0
Data type: Uint16
Change during operation: True
Set the integral gain for the field weakening controller.
Parameter 14-39 Torque Change Threshold Limit
Table 731: Parameter 14-39 Torque Change Threshold Limit
14-39 Torque Change Threshold Limit
Default value: 20%
Parameter type: Range, 10 - 100%
Setup: All setups
Conversion index: 67
Data type: Uint16
Change during operation: True
Set the torque change threshold limit in % of the actual torque. When the actual torque exceeds the torque threshold value, the
drive trips within 10 ms.
5.14.5 14-4* Energy Optimizing
Parameters for adjusting the energy optimization level in both variable torque (VT) and automatic energy optimization (AEO) mode
in parameter 1-03 Torque Characteristics.
Parameter 14-40 VT Level
Table 732: Parameter 14-40 VT Level
14-40 VT Level
Default value: 66%
Parameter type: Range, 40 - 90%
Setup: All setups
Conversion index: 0
Data type: Uint8
Change during operation: False
N O T I C E
This parameter cannot be adjusted while the motor is running.
N O T I C E
This parameter is not active when parameter 1-10 Motor Construction is set to [1] PM non-salient SPM.
Enter the level of motor magnetization at low speed. Selection of a low value reduces energy loss in the motor but also reduces load
capability.
Parameter 14-41 AEO Minimum Magnetisation
Table 733: Parameter 14-41 AEO Minimum Magnetisation
14-41 AEO Minimum Magnetisation
Default value: Size related
Parameter type: Range, 30 - 200%
Setup: All setups
Conversion index: 0
Data type: Uint8
Change during operation: True
N O T I C E
This parameter is not active when parameter 1-10 Motor Construction is set to [1] PM non-salient SPM.
Enter the minimum allowable magnetization for AEO. Selection of a low value reduces energy loss in the motor but can also reduce
resistance to sudden load changes.
AU275636650261en-000101 / 130R0334 | 465Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 Series and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals