Parameter 40-44 Fault Log: DC Link Voltage
Table 1360: Parameter 40-44 Fault Log: DC Link Voltage
40-44 Fault Log: DC Link Voltage
Parameter type: Range, 0 - 10000 V, Array [10]
Change during operation: False
View the DC-link voltage when the logged event occurred.
Parameter 40-45 Fault Log: Control Word
Table 1361: Parameter 40-45 Fault Log: Control Word
40-45 Fault Log: Control Word
Parameter type: Range, 0 - 65535, Array [10]
Change during operation: False
View the control word sent from the drive when the logged event occurred.
Parameter 40-46 Fault Log: Status Word
Table 1362: Parameter 40-46 Fault Log: Status Word
40-46 Fault Log: Status Word
Parameter type: Range, 0 - 65535, Array [10]
Change during operation: False
View the status word sent from the drive when the logged event occurred.
5.30.4 40-5* Advanced Control Settings
Parameters for configuring the advanced motor control settings.
Parameter 40-50 Flux Sensorless Model Shift
Table 1363: Parameter 40-50 Flux Sensorless Model Shift
40-50 Flux Sensorless Model Shift
Default value: Size related
Change during operation: True
Use this parameter to enable or disable the shifting between flux model 1 and flux model 2 at low speed. See also parameter 1-66
Min. Current at Low Speed.
Parameter 40-51 Flux Sensorless Corr. Gain
Table 1364: Parameter 40-51 Flux Sensorless Corr. Gain
40-51 Flux Sensorless Corr. Gain
Default value: Size related
Parameter type: Range, 0.1 - 200.0
Change during operation: True
Adjust the flux correction gain used at low speed.
AU275636650261en-000101 / 130R0334 | 665Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide