Troubleshooting
Check if the motor shaft is locked.
Check if the start current triggers the current limit set in parameter 4-18 Current Limit.
Check if it increases the value in parameter 30-23 Locked Rotor Detection Time [s].
7.2.86 WARNING/ALARM 104, Mixing Fan Fault
Cause
The fan is not operating. The fan monitor checks that the fan is spinning at power-up or whenever the mixing fan is turned on. The
mixing fan fault can be configured as a warning or an alarm in parameter 14-53 Fan Monitor.
Troubleshooting
Cycle power to the drive to determine if the warning/alarm returns.
7.2.87 WARNING/ALARM 122, Mot. Rotat. Unexp.
Cause
The drive performs a function that requires the motor to be at standstill, for example DC hold for PM motors.
7.2.88 WARNING 123, Motor Mod. Changed
Cause
The motor selected in parameter 1-11 Motor Model is not correct.
Troubleshooting
Check the motor model.
7.2.89 WARNING/ALARM 157, Power Limit Mot.
Cause
The output power exceeds the value defined in parameter 4-82 Power Limit Motor Mode.
7.2.90 WARNING/ALARM 158, Power Limit Gen.
Cause
The generating power exceeds the value defined in parameter 4-83 Power Limit Generator Mode.
7.2.91 WARNING 163, ATEX ETR Cur.Lim.Warning
Cause
The drive has run above the characteristic curve for more than 50 s. The warning is activated at 83% and deactivated at 65% of the
allowed thermal overload.
7.2.92 ALARM 164, ATEX ETR Cur.Lim.Alarm
Cause
Running above the characteristic curve for more than 60 s within a period of 600 s activates the alarm, and the drive trips.
7.2.93 WARNING 165, ATEX ETR Freq.Lim.Warning
Cause
The drive has run for more than 50 s below the allowed minimum frequency (parameter 1-98 ATEX ETR Interpol. Points Freq.).
7.2.94 ALARM 166, ATEX ETR Freq.Lim.Alarm
Cause
The drive has run for more than 60 s (in a period of 600 s) below the allowed minimum frequency (parameter 1-98 ATEX ETR Interpol.
Points. Freq.).
7.2.95 WARNING/ALARM 210, Position Tracking
Cause
The actual position error exceeds the value in parameter 4-71 Maximum Position Error. Parameter 4-70 Position Error Function defines
whether this is a warning or an alarm.
AU275636650261en-000101 / 130R0334714 | Danfoss A/S © 2022.12
Troubleshooting
VLT AutomationDrive FC 301/302
Programming Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 Series and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals