6-16 Terminal 53 Filter Time Constant
Range: Function:
0.001 s* [0.001 - 10.000 s] Enter the time constant. This is a first-order digital low pass filter time constant for suppressing
electrical noise in terminal 53. A high time constant value improves dampening but also increases
the time delay through the filter.
This parameter cannot be adjusted while the motor is running.
3.8.4 6-2* Analog Input 2
Parameters for configuring the scaling and limits for analog input 2 (terminal 54).
6-20 Terminal 54 Low Voltage
Range: Function:
0.07 V* [Application dependant] Enter the low voltage value. This analog input scaling value should correspond to the minimum
reference value, set in par. 3-02
Minimum Reference
. See also the section
Reference Handling
.
6-21 Terminal 54 High Voltage
Range: Function:
10.00 V* [Application dependant] Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par. 6-25
Terminal 54 High Ref./Feedb. Value
.
6-22 Terminal 54 Low Current
Range: Function:
0.14 mA* [Application dependant] Enter the low current value. This reference signal should correspond to the minimum reference
value, set in par. 3-02
Minimum Reference
. The value must be set at >2 mA in order to activate the
Live Zero Time-out Function in par. 6-01
Live Zero Timeout Function
.
6-23 Terminal 54 High Current
Range: Function:
20.00 mA* [Application dependant] Enter the high current value corresponding to the high reference/feedback value set in
par. 6-25
Terminal 54 High Ref./Feedb. Value
.
6-24 Terminal 54 Low Ref./Feedb. Value
Range: Function:
0 Referen-
ceFeedback-
Unit*
[-999999.999 - 999999.999 Refer-
enceFeedbackUnit]
Enter the analog input scaling value that corresponds to the minimum reference feedback value set
in par. 3-02
Minimum Reference
.
6-25 Terminal 54 High Ref./Feedb. Value
Range: Function:
Application
dependent*
[-999999.999 - 999999.999 Refer-
enceFeedbackUnit]
Enter the analog input scaling value that corresponds to the maximum reference feedback value set
in par. 3-03
Maximum Reference
.
6-26 Terminal 54 Filter Time Constant
Range: Function:
0.001 s* [0.001 - 10.000 s] Enter the time constant. This is a first-order digital low pass filter time constant for suppressing
electrical noise in terminal 54. A high time constant value improves dampening but also increases
the time delay through the filter.
This parameter cannot be adjusted while the motor is running.
3 Parameter descriptions FC 300 Programming Guide
118
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
3

Other manuals for Danfoss VLT AutomationDrive FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300
CategoryDC Drives
LanguageEnglish

Related product manuals