16-70 Pulse Output #29 [Hz]
Range: Function:
0* [0 - 40000 ] View the actual value of pulses at terminal 29 in digital output mode.
This parameter is available for FC 302 only.
16-71 Relay Output [bin]
Range: Function:
0 N/A* [0 - 511 N/A] View the settings of all relays.
16-72 Counter A
Range: Function:
0* [-2147483648 - 2147483647 ] View the present value of Counter A. Counters are useful as comparator operands, see
par. 13-10
Comparator Operand
.
The value can be reset or changed either via digital inputs (parameter group 5-1*) or by using an
SLC action (par. 13-52
SL Controller Action
).
16-73 Counter B
Range: Function:
0* [-2147483648 - 2147483647 ] View the present value of Counter B. Counters are useful as comparator operands
(par. 13-10
Comparator Operand
).
The value can be reset or changed either via digital inputs (parameter group 5-1*) or by using an
SLC action (par. 13-52
SL Controller Action
).
16-74 Prec. Stop Counter
Range: Function:
0* [0 - 2147483647 ] Returns the actual counter value of precise counter (par. 1-84
Precise Stop Counter Value
).
16-75 Analog In X30/11
Range: Function:
0.000 N/A* [-20.000 - 20.000 N/A] View the actual value at input X30/11 of MCB 101.
16-76 Analog In X30/12
Range: Function:
0.000 N/A* [-20.000 - 20.000 N/A] View the actual value at input X30/12 of MCB 101.
16-77 Analog Out X30/8 [mA]
Range: Function:
0.000 N/A* [0.000 - 30.000 N/A] View the actual value at input X30/8 in mA.
16-78 Analog Out X45/1 [mA]
Range: Function:
0.000* [0.000 - 30.000 ] View the actual value at output X45/1. The value shown reflects the selection in par. 6-70
Terminal
X45/1 Output
.
3 Parameter descriptions FC 300 Programming Guide
218
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
3