0-02 Motor Speed Unit
Option: Function:
This parameter cannot be adjusted while the motor is running.
The display showing depends on settings in par. 0-02
Motor Speed Unit
and par. 0-03
Regional
Settings
. The default setting of par. 0-02
Motor Speed Unit
and par. 0-03
Regional Settings
depends
on which region of the world the frequency converter is supplied to, but can be re-programmed as
required.
NB!
Changing the
Motor Speed Unit
will reset certain parameters to their initial value.
It is recommended to select the motor speed unit first, before modifying other
parameters.
[0] RPM Selects display of motor speed variables and parameters (i.e. references, feedbacks and limits) in
terms of motor speed (RPM).
[1] * Hz Selects display of motor speed variables and parameters (i.e. references, feedbacks and limits) in
terms of output frequency to the motor (Hz).
0-03 Regional Settings
Option: Function:
[0] * International Activates par. 1-20
Motor Power [kW]
for setting the motor power in kW and sets the default value
of par. 1-23
Motor Frequency
to 50 Hz.
[1] US Activates par. 1-20
Motor Power [kW]
for setting the motor power in HP and sets the default value
of par. 1-23
Motor Frequency
to 60 Hz.
This parameter cannot be adjusted while the motor is running.
0-04 Operating State at Power-up (Hand)
Option: Function:
Selects the operating mode upon reconnection of the frequency converter to mains voltage after
power down in Hand (local) operation mode.
[0] Resume Restarts the frequency converter maintaining the same local reference and the same start/stop
settings (applied by [HAND ON/OFF]) as before the frequency converter was powered down.
[1] * Forced stop, ref=old Restarts the frequency converter with a saved local reference, after mains voltage reappears and
after pressing [HAND ON].
[2] Forced stop, ref=0 Resets the local reference to 0 upon restarting the frequency converter.
3.2.3 0-1* Set-up Operations
Define and control the individual parameter setups.
The frequency converter has four parameter setups that can be programmed independently of each other. This makes the frequency converter very
flexible and able to solve advanced control functionality problems, often saving the cost of external control equipment. For example these can be used
to program the frequency converter to operate according to one control scheme in one setup (e.g. motor 1 for horizontal movement) and another control
scheme in another setup (e.g. motor 2 for vertical movement). Alternatively they can be used by an OEM machine builder to identically program all their
factory fitted frequency converters for different machine types within a range to have the same parameters and then during production/commissioning
simply select a specific setup depending on which machine the frequency converter is installed on.
FC 300 Programming Guide 3 Parameter descriptions
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
31
3

Other manuals for Danfoss VLT AutomationDrive FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300
CategoryDC Drives
LanguageEnglish

Related product manuals