The active setup (i.e. the setup in which the frequency converter is currently operating) can be selected in par. 0-10
Active Set-up
and is displayed in
the LCP. Using Multi set-up it is possible to switch between setups with the frequency converter running or stopped, via digital input or serial communication
commands. If it is necessary to change setups whilst running, ensure par. 0-12
This Set-up Linked to
is programmed as required. Using par. 0-11
Edit
Set-up
it is possible to edit parameters within any of the setups whilst continuing the frequency converter operation in its Active Setup which can be a
different setup to that being edited. Using par. 0-51
Set-up Copy
it is possible to copy parameter settings between the setups to enable quicker com-
missioning if similar parameter settings are required in different setups.
0-10 Active Set-up
Option: Function:
Select the set-up to control the frequency converter functions.
[0] Factory setup Cannot be changed. It contains the Danfoss data set, and can be used as a data source when
returning the other set-ups to a known state.
[1] * Set-up 1
Set-up 1
[1] to
Set-up 4
[4] are the four separate parameter set-ups within which all parameters
can be programmed.
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[9] Multi Set-up Remote selection of set-ups using digital inputs and the serial communication port. This set-up uses
the settings from par. 0-12
This Set-up Linked to
. Stop the frequency converter before making
changes to open- and closed loop functions
Use par. 0-51
Set-up Copy
to copy a set-up to one or all other set-ups. Stop the frequency converter before switching between set-ups where parameters
marked ‘not changeable during operation’ have different values. To avoid conflicting settings of the same parameter within two different set-ups, link the
set-ups together using par. 0-12
This Set-up Linked to
. Parameters which are ‘not changeable during operation’ are marked FALSE in the parameter lists
in the section
Parameter Lists
.
0-11 Edit Set-up
Option: Function:
Select the set-up to be edited (i.e. programmed) during operation; either the active set-up or one
of the inactive set-ups.
[0] Factory setup Cannot be edited but it is useful as a data source to return the other set-ups to a known state.
[1] * Set-up 1
Set-up 1
[1] to
Set-up 4
[4] can be edited freely during operation, independently of the active set-
up.
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[9] Active Set-up Can also be edited during operation. Edit the chosen set-up from a range of sources: LCP, FC RS485,
FC USB or up to five fieldbus sites.
3 Parameter descriptions FC 300 Programming Guide
32
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark