The active setup (i.e. the setup in which the frequency converter is currently operating) can be selected in par. 0-10
Active Set-up
and is displayed in
the LCP. Using Multi set-up it is possible to switch between setups with the frequency converter running or stopped, via digital input or serial communication
commands. If it is necessary to change setups whilst running, ensure par. 0-12
This Set-up Linked to
is programmed as required. Using par. 0-11
Edit
Set-up
it is possible to edit parameters within any of the setups whilst continuing the frequency converter operation in its Active Setup which can be a
different setup to that being edited. Using par. 0-51
Set-up Copy
it is possible to copy parameter settings between the setups to enable quicker com-
missioning if similar parameter settings are required in different setups.
0-10 Active Set-up
Option: Function:
Select the set-up to control the frequency converter functions.
[0] Factory setup Cannot be changed. It contains the Danfoss data set, and can be used as a data source when
returning the other set-ups to a known state.
[1] * Set-up 1
Set-up 1
[1] to
Set-up 4
[4] are the four separate parameter set-ups within which all parameters
can be programmed.
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[9] Multi Set-up Remote selection of set-ups using digital inputs and the serial communication port. This set-up uses
the settings from par. 0-12
This Set-up Linked to
. Stop the frequency converter before making
changes to open- and closed loop functions
Use par. 0-51
Set-up Copy
to copy a set-up to one or all other set-ups. Stop the frequency converter before switching between set-ups where parameters
marked ‘not changeable during operation’ have different values. To avoid conflicting settings of the same parameter within two different set-ups, link the
set-ups together using par. 0-12
This Set-up Linked to
. Parameters which are ‘not changeable during operation’ are marked FALSE in the parameter lists
in the section
Parameter Lists
.
0-11 Edit Set-up
Option: Function:
Select the set-up to be edited (i.e. programmed) during operation; either the active set-up or one
of the inactive set-ups.
[0] Factory setup Cannot be edited but it is useful as a data source to return the other set-ups to a known state.
[1] * Set-up 1
Set-up 1
[1] to
Set-up 4
[4] can be edited freely during operation, independently of the active set-
up.
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[9] Active Set-up Can also be edited during operation. Edit the chosen set-up from a range of sources: LCP, FC RS485,
FC USB or up to five fieldbus sites.
3 Parameter descriptions FC 300 Programming Guide
32
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
3

Other manuals for Danfoss VLT AutomationDrive FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300
CategoryDC Drives
LanguageEnglish

Related product manuals