0-51 Set-up Copy
Option: Function:
[0] * No copy No function
[1] Copy to set-up 1 Copies all parameters in the present Programming Set-up (defined in par. 0-11
Programming Set-
up
) to Set-up 1.
[2] Copy to set-up 2 Copies all parameters in the present Programming Set-up (defined in par. 0-11
Programming Set-
up
) to Set-up 2.
[3] Copy to set-up 3 Copies all parameters in the present Programming Set-up (defined in par. 0-11
Programming Set-
up
) to Set-up 3.
[4] Copy to set-up 4 Copies all parameters in the present Programming Set-up (defined in par. 0-11
Programming Set-
up
) to Set-up 4.
[9] Copy to all Copies the parameters in the present set-up over to each of the set-ups 1 to 4.
3.2.8 0-6* Password
Define password access to menus.
0-60 Main Menu Password
Range: Function:
100 N/A* [0 - 999 N/A] Define the password for access to the Main Menu via the [Main Menu] key. If par. 0-61
Access to
Main Menu w/o Password
is set to
Full access
[0], this parameter will be ignored.
0-61 Access to Main Menu w/o Password
Option: Function:
[0] * Full access Disables password defined in par. 0-60
Main Menu Password
.
[1] LCP: Read only Prevent unauthorized editing of Main Menu parameters.
[2] LCP: No access Prevent unauthorized viewing and editing of Main Menu parameters.
[3] Bus: Read only Read-only functions for parameters on fieldbus and/or FC standard bus.
[4] Bus: No access No access to parameters is allowed via fieldbus and/or FC standard bus.
[5] All: Read only Read-only function for parameters on LCP, fieldbus or FC standard bus.
[6] All: No access No access from LCP, fieldbus or FC standard bus is allowed.
If
Full access
[0] is selected then par. 0-60
Main Menu Password
, par. 0-65
Personal Menu Password
and par. 0-66
Access to Personal Menu w/o
Password
will be ignored.
0-65 Quick Menu Password
Range: Function:
200* [-9999 - 9999 ] Define the password for access to the Quick Menu via the [Quick Menu] key. If par. 0-66
Access to
Quick Menu w/o Password
is set to
Full access
[0], this parameter will be ignored.
FC 300 Programming Guide 3 Parameter descriptions
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
43
3