0-12 This Set-up Linked to
Option: Function:
To enable conflict-free changes from one set-up to another during operation, link set-ups containing
parameters which are not changeable during operation. The link will ensure synchronising of the
‘not changeable during operation’ parameter values when moving from one set-up to another during
operation. ‘Not changeable during operation’ parameters can be identified by the label FALSE in the
parameter lists in the section
Parameter Lists
.
Par. 0-12
This Set-up Linked to
is used by Multi set-up in par. 0-10
Active Set-up
. Multi set-up is
used to move from one set-up to another during operation (i.e. while the motor is running).
Example:
Use Multi set-up to shift from Set-up 1 to Set-up 2 whilst the motor is running. Programme in Set-
up 1 first, then ensure that Set-up 1 and Set-up 2 are synchronised (or ‘linked’). Synchronisation
can be performed in two ways:
1. Change the edit set-up to
Set-up 2
[2] in par. 0-11
Edit Set-up
and set par. 0-12
This Set-up
Linked to
to
Set-up 1
[1]. This will start the linking (synchronising) process.
OR