[173] ft WG
[180] HP
0-31 Min Value of User-defined Readout
Range: Function:
0.00 Cus-
tomReadou-
tUnit*
[Application dependant] This parameter sets the min. value of the custom defined readout (occurs at zero speed). Only
possible to set different from 0 is when selecting a linear unit in par. 0-30
Unit for User-defined
Readout
. For Quadratic and Cubic units the minimum value will be 0.
0-32 Custom Readout Max Value
Range: Function:
100.00 Cus-
tomReadou-
tUnit*
[Application dependant] This parameter sets the max value to be shown when the speed of the motor has reached the set
value for par. 4-13
Motor Speed High Limit [RPM]
or par. 4-14
Motor Speed High Limit [Hz]
(depends
on setting in par. 0-02
Motor Speed Unit
).
0-37 Display Text 1
Range: Function:
0* [0 - 0 ] Enter a text which can be viewed in the graphical display by selecting Display Text 1 [37] in par.
0-20, 0-21, 0-22, 0-23 or 0-24.
0-38 Display Text 2
Range: Function:
0* [0 - 0 ] Enter a text which can be viewed in the graphical display by selecting Display Text 2 [38] in par.
0-20, 0-21, 0-22, 0-23 or 0-24.
0-39 Display Text 3
Range: Function:
0* [0 - 0 ] Enter a text which can be viewed in the graphical display by selecting Display Text 3 [39] in par.
0-20, 0-21, 0-22, 0-23 or 0-24.
3.2.6 LCP Keypad, 0-4*
Enable, disable and password protect individual keys on the LCP.
0-40 [Hand on] Key on LCP
Option: Function:
[0] Disabled No effect when [Hand on] is pressed. Select [0] Disabled to avoid accidental start of the drive in
Hand on
mode.
[1] * Enabled The LCP switches to
Hand on
mode directly when [Hand on] is pressed.
[2] Password After pressing [Hand on] a password is required. If par. 0-40 is in included in
My Personal Menu
,
define the password in par. 0-65,
Personal Menu Password
. Otherwise define the password in par.
0-60,
Main Menu Password
[3] Hand Off/On When [Hand on] is pressed once, the LCP switches to
Off
mode. When pressed again, the LCP
switches to
Hand on
mode.
[4] Hand Off/On w. Passw. Same as [3] but a password is required (see [2]).
FC 300 Programming Guide 3 Parameter descriptions
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
41
3

Other manuals for Danfoss VLT AutomationDrive FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300
CategoryDC Drives
LanguageEnglish

Related product manuals