5.2.9 8-** Comm. and Options
Param
eter
numb
er
Parameter description Default value 4 set-up Change
during
operation
Conversion
index
Type
8-0* General Settings
8-01 Control Site [0] Digital and ctrl.word All set-ups TRUE Uint8
8-02 Control Word Source ExpressionLimit All set-ups TRUE Uint8
8-03 Control Word Timeout Time 1 s 1 set-up TRUE -1 Uint32
8-04 Control Word Timeout Function ExpressionLimit 1 set-up TRUE Uint8
8-05 End-of-Timeout Function [1] Resume set-up 1 set-up TRUE Uint8
8-06 Reset Control Word Timeout [0] Do not reset All set-ups TRUE Uint8
8-07 Diagnosis Trigger [0] Disable 2 set-ups TRUE Uint8
8-08 Readout Filtering ExpressionLimit All set-ups TRUE Uint8
8-1* Ctrl. Word Settings
8-10 Control Word Prole [0] FC prole All set-ups TRUE Uint8
8-13 Congurable Status Word STW [1] Prole default All set-ups TRUE Uint8
8-14 Congurable Control Word CTW [1] Prole default All set-ups TRUE Uint8
8-19 Product Code ExpressionLimit 1 set-up TRUE 0 Uint32
8-3* FC Port Settings
8-30 Protocol [0] FC 1 set-up TRUE Uint8
8-31 Address 1 N/A 1 set-up TRUE 0 Uint8
8-32 FC Port Baud Rate ExpressionLimit 1 set-up TRUE Uint8
8-33 Parity / Stop Bits [0] Even Parity, 1 Stop Bit 1 set-up TRUE Uint8
8-34 Estimated cycle time 0 ms 2 set-ups TRUE -3 Uint32
8-35 Minimum Response Delay 10 ms 1 set-up TRUE -3 Uint16
8-36 Max Response Delay ExpressionLimit 1 set-up TRUE -3 Uint16
8-37 Max Inter-Char Delay ExpressionLimit 1 set-up TRUE -5 Uint16
8-4* FC MC protocol set
8-40 Telegram Selection [1] Standard telegram 1 2 set-ups TRUE Uint8
8-41 Parameters for Signals 0 All set-ups FALSE Uint16
8-42 PCD Write Conguration ExpressionLimit 2 set-ups TRUE 0 Uint16
8-43 PCD Read Conguration ExpressionLimit 2 set-ups TRUE 0 Uint16
8-5* Digital/Bus
8-50 Coasting Select [3] Logic OR All set-ups TRUE Uint8
8-51 Quick Stop Select [3] Logic OR All set-ups TRUE Uint8
8-52 DC Brake Select ExpressionLimit All set-ups TRUE Uint8
8-53 Start Select [3] Logic OR All set-ups TRUE Uint8
8-54 Reversing Select ExpressionLimit All set-ups TRUE Uint8
8-55 Set-up Select [3] Logic OR All set-ups TRUE Uint8
8-56 Preset Reference Select [3] Logic OR All set-ups TRUE Uint8
8-57 Prodrive OFF2 Select [3] Logic OR All set-ups TRUE Uint8
8-58 Prodrive OFF3 Select [3] Logic OR All set-ups TRUE Uint8
8-8* FC Port Diagnostics
8-80 Bus Message Count 0 N/A All set-ups TRUE 0 Uint32
8-81 Bus Error Count 0 N/A All set-ups TRUE 0 Uint32
8-82 Slave Messages Rcvd 0 N/A All set-ups TRUE 0 Uint32
8-83 Slave Error Count 0 N/A All set-ups TRUE 0 Uint32
8-84 Slave Messages Sent 0 N/A All set-ups TRUE 0 Uint32
8-85 Slave Timeout Errors 0 N/A All set-ups TRUE 0 Uint32
8-88 Reset FC port Diagnostics [0] Do not reset All set-ups TRUE Uint8
8-9* Bus Jog
8-90 Bus Jog 1 Speed ExpressionLimit All set-ups TRUE 67 Uint16
Parameter Lists VLT® AutomationDrive FC 361
168 Danfoss A/S © 03/2019 All rights reserved. MG06J202