8-85 Slave Timeout Errors
Range: Function:
0* [0 - 0 ] This parameter shows the number
of slave timeout errors.
8-88 Reset FC port Diagnostics
Reset all FC port diagnostic counters.
Option: Function:
[0] * Do not reset
[1] Reset counter
4.9.7 8-9* Bus Jog
8-90 Bus Jog 1 Speed
Range: Function:
Size
related*
[ 0 - par. 4-13
RPM]
Enter the jog speed. Activate this
xed jog speed via the serial port
or eldbus option.
8-91 Bus Jog 2 Speed
Range: Function:
Size
related*
[ 0 - par. 4-13
RPM]
Enter the jog speed. Activate this
xed jog speed via the serial port
or eldbus option.
4.10 Parameters: 9-** PROFIBUS
9-00 Setpoint
Range: Function:
0* [0 - 65535 ] This parameter receives cyclic
reference from a Master Class 2. If
the control priority is set to Master
Class 2, the reference for the
frequency converter is taken from
this parameter, whereas the cyclic
reference is ignored.
9-07 Actual Value
Range: Function:
0* [0 - 65535 ] This parameter delivers the MAV for
a Master Class 2. This parameter is
valid if the control priority is set to
Master Class 2.
9-15 PCD Write Conguration
Array [10]
Option: Function:
Select the parameters to be
assigned to PCD 3–10 of the
telegrams. The number of available
PCDs depends on the telegram
type. The values in PCD 3–10 are
then written to the selected
parameters as data values. Alterna-
tively, specify a standard PROFIBUS
telegram in parameter 9-22 Telegram
Selection.
[0] None
[302] Minimum
Reference
[303] Maximum
Reference
[312] Catch up/slow
Down Value
[341] Ramp 1 Ramp
Up Time
[342] Ramp 1 Ramp
Down Time
[351] Ramp 2 Ramp
Up Time
[352] Ramp 2 Ramp
Down Time
[380] Jog Ramp
Time
[381] Quick Stop
Ramp Time
[411] Motor Speed
Low Limit
[RPM]
[412] Motor Speed
Low Limit [Hz]
[413] Motor Speed
High Limit
[RPM]
[414] Motor Speed
High Limit
[Hz]
[416] Torque Limit
Motor Mode
[417] Torque Limit
Generator
Mode
[553] Term. 29 High
Ref./Feedb.
Value
[558] Term. 33 High
Ref./Feedb.
Value
Parameter Descriptions VLT® AutomationDrive FC 361
104 Danfoss A/S © 03/2019 All rights reserved. MG06J202
44

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 361

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 361 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 361 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 361
CategoryDC Drives
LanguageEnglish

Related product manuals