0-51 Set-up Copy
Option: Function:
[0] * No copy No function.
[1] Copy to set-up
1
Copies all parameters in the present
programming set-up (dened in
parameter 0-11 Programming Set-up)
to set-up 1.
[2] Copy to set-up
2
Copies all parameters in the present
programming set-up (dened in
parameter 0-11 Programming Set-up)
to set-up 2.
[3] Copy to set-up
3
Copies all parameters in the present
programming set-up (dened in
parameter 0-11 Programming Set-up)
to set-up 3.
[4] Copy to set-up
4
Copies all parameters in the present
programming set-up (dened in
parameter 0-11 Programming Set-up)
to set-up 4.
[9] Copy to all Copies the parameters in the
present set-up to each of the set-
ups 1 to 4.
4.1.7 0-6* Password
0-60 Main Menu Password
Range: Function:
100* [0 - 999 ] Dene the password for access to
the Main Menu via the [Main Menu]
key. If parameter 0-61 Access to Main
Menu w/o Password is set to [0] Full
access, this parameter is ignored.
0-61 Access to Main Menu w/o Password
Option: Function:
[0] * Full access Disables password dened in
parameter 0-60 Main Menu
Password.
[1] Read only Prevent unauthorized editing of
Main Menu parameters.
[2] No access Prevent unauthorized viewing and
editing of Main Menu parameters.
If [0] Full access is selected, parameter 0-60 Main Menu
Password, parameter 0-65 Personal Menu Password, and
parameter 0-66 Access to Personal Menu w/o Password are
ignored.
4.2
Parameters: 1-** Load and Motor
4.2.1 1-0* General Settings
Dene whether the frequency converter operates in speed
mode or torque mode, and whether the internal PID
control should be active or not.
1-00 Conguration Mode
Option: Function:
Select the application control
principle to be used when a remote
reference (that is via analog input
or eldbus) is active. A remote
reference can only be active when
parameter 3-13 Reference Site is set
to [0] Linked to Hand/Auto or [1]
Remote.
[0] Speed open
loop
Enables speed control (without
feedback signal from motor) with
automatic slip compensation for
almost constant speed at varying
loads.
Compensations are active, but can
be disabled in parameter group 1-0*
General Settings. Set the speed
control parameters in parameter
group 7-0* Speed PID Ctrl.
[1] Speed closed
loop
Enables speed closed-loop control
with feedback. Obtain full holding
torque at 0 RPM.
For increased speed accuracy,
provide a feedback signal and set
the speed PID control. Set the
speed control parameters in
parameter group 7-0* Speed PID Ctrl.
[3] Process Enables the use of process control
in the frequency converter. Set the
process control parameters in
parameter groups 7-2* Process Ctrl.
Feedb. and 7-3* Process PID Ctrl.
[4] Torque open
loop
Enables the use of torque open
loop in VVC
+
mode
(parameter 1-01 Motor Control
Principle). Set the torque PID
parameters in parameter group 7-1*
Torque PI Control.
[7] Extended PID
Speed OL
Specic parameters in parameter
groups 7-2* Process Ctrl. Feedb. to
7-5* Ext. Process PID Ctrl.
Parameter Descriptions VLT® AutomationDrive FC 361
32 Danfoss A/S © 03/2019 All rights reserved. MG06J202
44