Number Description Warning Alarm/
trip
Alarm/
trip lock
Parameter
reference
1 10 volts low X
2 Live zero error (X) (X) Parameter 6-01 Live Zero Timeout Function
3 No motor (X) Parameter 1-80 Function at Stop
4 Mains phase loss (X) (X) (X) Parameter 14-12 Response to Mains
Imbalance
5 DC-link voltage high X
6 DC-link voltage low X
7 DC overvoltage X X
8 DC undervoltage X X
9 Inverter overloaded X X
10 Motor ETR overtemperature (X) (X) Parameter 1-90 Motor Thermal Protection
11 Motor thermistor overtemperature (X) (X) Parameter 1-90 Motor Thermal Protection
12 Torque limit X X
13 Over current X X X
14 Ground fault X X
15 Hardware mismatch X X
16 Short circuit X X
17 Control word timeout (X) (X) Parameter 8-04 Control Word Timeout
Function
18 Start failed X
21 Param error X
23 Internal fans X
24 External fans X
29 Heat sink temp X X X
30 Motor phase U missing (X) (X) (X) Parameter 4-58 Missing Motor Phase Function
31 Motor phase V missing (X) (X) (X) Parameter 4-58 Missing Motor Phase Function
32 Motor phase W missing (X) (X) (X) Parameter 4-58 Missing Motor Phase Function
33 Inrush fault X X
34 Fieldbus communication fault X X
35 Option fault X
36 Mains failure X X
37 Imbalance of supply voltage X
38 Internal fault X X
39 Heat sink sensor X X
40 Overload of digital output terminal 27 (X) Parameter 5-00 Digital I/O Mode,
parameter 5-01 Terminal 27 Mode
41 Overload of digital output terminal 29 (X) Parameter 5-00 Digital I/O Mode,
parameter 5-02 Terminal 29 Mode
42 Ovrld X30/6-7 (X)
45 Ground fault 2 X X
46 Pwr. card supply X X
47 24 V supply low X X X
48 1.2 V supply low X X
49 Speed limit X
50 AMA calibration failed X
51 AMA check U
nom
and I
nom
X
52 AMA low I
nom
X
53 AMA motor too big X
54 AMA motor too small X
55 AMA parameter out of range X
56 AMA interrupted by user X
57 AMA time-out X
Troubleshooting Programming Guide
MG06J202 Danfoss A/S © 03/2019 All rights reserved. 179
6
6

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 361

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 361 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 361 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 361
CategoryDC Drives
LanguageEnglish

Related product manuals