5 = Rectier module.
6 = Right rectier module.
ALARM 247, Power card temperature
The supply on the power card is out of range.
The report value in the alarm log indicates which power
module generated the alarm:
1 = Leftmost inverter module.
2 = Middle inverter module.
2 = Right inverter module.
2 = Second drive from the left inverter module.
3 = Right inverter module.
3 = Third from the left inverter module.
4 = Far right inverter module.
5 = Rectier module.
6 = Right rectier module.
ALARM 248, Illegal power section conguration
Power size conguration fault on the power card.
The report value in the alarm log indicates which power
module generated the alarm:
1 = Leftmost inverter module.
2 = Middle inverter module.
2 = Right inverter module.
2 = Second drive from the left inverter module.
3 = Right inverter module.
3 = Third from the left inverter module.
4 = Far right inverter module.
5 = Rectier module.
6 = Right rectier module.
WARNING 249, Rect. low temperature
The temperature of the rectier heat sink is too low, which
indicates that the temperature sensor may be defect.
WARNING 250, New spare part
The power or switch mode supply has been exchanged.
Restore the drive type code in the EEPROM. Select the
correct type code in parameter 14-23 Typecode Setting
according to the label on the drive. Remember to select
Save to EEPROM at the end.
WARNING 251, New typecode
The power card or other components are replaced, and the
type code has changed.
Troubleshooting VLT® AutomationDrive FC 361