[2] Drive ready The frequency converter is ready for
operation
and applies a supply signal on
the control board.
[3] Drive ready /
remote
control
The frequency converter is ready for
operation and is in Auto On mode.
[4] Stand-by / no
warning
The frequency converter is ready for
operation.
No start or stop command is
been given (start/disable). There are no
warnings.
[5] Running The motor is running.
[6] Running / no
warning
The output speed is higher than the
speed
set in 1-81 Min Speed for Function at
Stop [RPM]. The motor is running and
there are no warnings.
[8] Run on
reference
/ no
warning
The motor runs at reference speed.
[9] Alarm An alarm activates the output. There are
no
warnings.
[10] Alarm or
warning
An alarm or a warning activates the
output.
[11] At torque limit
The torque limit set in 4-16
Torque Limit
Motor Mode or 1-17 Voltage filter time
const. has been exceeded.
[12] Out of current
range
The motor current is outside the range set
in 4-18
Current Limit.
[13] Below current,
low
The motor current is lower than set in
4-50
Warning Current Low.
[14] Above current,
high
The motor current is higher than set in
4-51
Warning Current High.
[15] Out of speed
range
The output speed is outside the range set
in 4-52
Warning Speed Low and
4-53 Warning Speed High.
[16] Below speed,
low
The output speed is lower than the
setting
in 4-52 Warning Speed Low.
[17] Above speed,
high
The output speed is higher than the
setting
in 4-53 Warning Speed High.
[18] Out of
feedback
range
The feedback is outside the range set in
4-56
Warning Feedback Low and
4-57 Warning Feedback High.
[19] Below
feedback
low
The feedback is below the limit set in
4-56 Warning Feedback Low.
[20] Above
feedback
high
The feedback is above the limit set in
4-57 Warning Feedback High.
[21] Thermal
warning
The thermal warning turns on when the
temperature
exceeds the limit in the
motor, the frequency converter, the brake
resistor, or the thermistor.
[25] Reverse
Reversing. Logic ‘1’ = relay
activated, 24 V
DC when CW rotation of the motor. Logic
‘0’ = relay not activated, no signal, when
CCW rotation of the motor.
[26] Bus OK Active communication (no time-out) via
the
serial communication port.
[27] Torque limit
and
stop
Use in performing a coasting stop and in
torque limit condition. If the frequency
converter has received a stop signal and is
at
the torque limit, the signal is Logic ‘0’.
[28] Brake, no
warning
The brake is active and there are no
warnings.
[29] Brake ready,
no
fault
The brake is ready for operation and there
are no faults.
[30] Brake fault
(IGBT)
The output is Logic ‘1’ when the brake
IGBT
is short-circuited. Use this function to
protect the frequency converter if there is
a fault on the brake modules. Use the
output/relay to cut out the main voltage
from the frequency converter.
[35] External
Interlock
External Interlock function has been
activated
via one of the digital inputs.
[40] Out of ref
range
[41] Below
reference
low
[42] Above
reference
high
[45] Bus Ctrl
[46] Bus Ctrl 1 if
timeout
[47] Bus Ctrl 0 if
timeout
[55] Pulse output
[60] Comtor 0 See parameter group 13-1*. If Comtor 0 is
evaluated
as TRUE, the output will go
high. Otherwise, it will be low.
[61] Comtor 1 See parameter group 13-1*. If Comtor 2 is
evaluated
as TRUE, the output will go
high. Otherwise, it will be low.
[62] Comtor 2 See parameter group 13-1*. If Comtor 2 is
evaluated
as TRUE, the output will go
high. Otherwise, it will be low.
[63] Comtor 3 See parameter group 13-1*. If Comtor 3 is
evaluated
as TRUE, the output will go
high. Otherwise, it will be low.
[64] Comtor 4 See parameter group 13-1*. If Comtor 4 is
evaluated
as TRUE, the output will go
high. Otherwise, it will be low.
[65] Comtor 5 See parameter group 13-1*. If Comtor 5 is
evaluated
as TRUE, the output will go
high. Otherwise, it will be low.
[70] Logic Rule 0 See parameter group 13-4*. If Logic Rule 0
is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[71] Logic Rule 1 See parameter group 13-4*. If Logic Rule 1
is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[72] Logic Rule 2 See parameter group 13-4*. If Logic Rule 2
is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[73] Logic Rule 3 See parameter group 13-4*. If Logic Rule 3
is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
64 MG16H102 - VLT
®
is a registered Danfoss trademark
33

Table of Contents