5-40 Function Relay
Select options to define the function of the relays.
The
selection of each mechanical relay is realised in an array
meter.
Option: Function:
Array [8] (Relay 1 [0], Relay 2 [1],
Option
MCB 105: Relay 7 [6], Relay
8 [7] and Relay 9 [8])
[0] * No operation
[1] Control Ready
[2] Drive ready
[3] Drive rdy/rem ctrl
[4] Standby / no warning
[5] * Running Default setting for relay 2.
[6] Running / no warning
[8] Run on ref/no warn
[9] * Alarm Default setting for relay 1.
[10] Alarm or warning
[11] At torque limit
[12] Out of current range
[13] Below current, low
[14] Above current, high
[15] Out of speed range
[16] Below speed, low
[17] Above speed, high
[18] Out of feedb. range
[19] Below feedback, low
[20] Above feedback, high
[21] Thermal warning
[25] Reverse
[26] Bus OK
[27] Torque limit & stop
[28] Brake, no brake war
[29] Brake ready, no fault
[30] Brake fault (IGBT)
[35] External Interlock
[36] Control word bit 11
[37] Control word bit 12
[40] Out of ref range
[41] Below reference, low
[42] Above ref, high
[45] Bus ctrl.
[46] Bus ctrl, 1 if timeout
[47] Bus ctrl, 0 if timeout
[60] Comparator 0
[61] Comparator 1
[62] Comparator 2
[63] Comparator 3
[64] Comparator 4
[65] Comparator 5
[70] Logic rule 0
[71] Logic rule 1
[72] Logic rule 2
5-40 Function Relay
Select options to define the function of the relays.
The
selection of each mechanical relay is realised in an array
meter.
Option: Function:
[73] Logic rule 3
[74] Logic rule 4
[75] Logic rule 5
[80] SL digital output A
[81] SL digital output B
[82] SL digital output C
[83] SL digital output D
[84] SL digital output E
[85] SL digital output F
[160] No alarm
[161] Running reverse
[165] Local ref active
[166] Remote ref active
[167] Start command activ
[168] Hand mode
[169] Auto mode
[180] Clock Fault
[181] Prev. Maintenance
[190] No-Flow
[191] Dry Pump
[192] End Of Curve
[193] Sleep Mode
[194] Broken Belt
[195] Bypass Valve Control
[199] Injection Control
[211] Pack Comp. 1
[212] Pack Comp. 2
[213] Pack Comp. 3
5-41 On Delay, Relay
Array [8](Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5
[4],
Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Range: Function:
0.01 s* [0.01 - 600 s] Enter the delay of the relay cut-in time.
Select
one of available mechanical relays
and MCB 105 in an array function. See
5-40 Function Relay.
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
MG16H102 - VLT
®