104•dap4UserManual
Manual Override Switches
For testing and during start-up each Data Aire gForce unit is provided with manual override slide
switches. There are seven slide switches. One for each of the following functions:
Water Valve Fan Speed
Humidier Heat 1
Cool 2 Cool 1
Blower
All automatic control is disabled but the safety switches remain functional. Simply slide the manual
switchestoenergizetheblower,compressors,humidication,reheatandotherfunctions.
The fan speed of the EC (Electronically Commutated) motor can be adjusted from 0 – 10 volts by
adjusting the potentiometer at the left of the Fan Speed switch. The fan will turn 10% for each volt
adjustment. One volt equals 10%. At ten volts the motor is at full speed.
Warning: Do not leave the unit in manual override. Slide the switches to the OFF position when
completing testing and/or start-up. An alarm will be activated if units are left in the ON position.