68•dap4UserManual
Current Temperature = Setpoint + Deadband + 0.6°F = 60% Position Open
Current Temperature = Setpoint + Deadband + 0.7°F = 70% Position Open
Current Temperature = Setpoint + Deadband + 0.8°F = 80% Position Open
Current Temperature = Setpoint + Deadband + 0.9°F = 90% Position Open
Current Temperature = Setpoint + Deadband + 1.0°F = 100% Position Open
7. The chilled water valve proportionally closes 10% for each 0.1°F below the temperature set
point plus 1°F.
8. If the current temperature is lower than at the last adjustment period, the following sequence is
used to determine the new valve position:
Current Temperature = Setpoint + 1.0°F = 100% Position Open
Current Temperature = Setpoint + 0.9°F = 90% Position Open
Current Temperature = Setpoint + 0.8°F = 80% Position Open
Current Temperature = Setpoint + 0.7°F = 70% Position Open
Current Temperature = Setpoint + 0.6°F = 60% Position Open
Current Temperature = Setpoint + 0.5°F = 50% Position Open
Current Temperature = Setpoint + 0.4°F = 40% Position Open
Current Temperature = Setpoint + 0.3°F = 30% Position Open
Current Temperature = Setpoint + 0.2°F = 20% Position Open
Current Temperature = Setpoint + 0.1°F = 10% Position Open
Current Temperature = Setpoint + 0.0°F = 0% Position Open
9. The dap4 will switch the unit to DX cooling for one (1) hour after every 100 hours of continuous
hoursofEnergySaverorAuxiliaryChilledWaterCooling.
ENERGY SAVER and AUXILIARY CHILLED WATER COOLING ASSIST
1.EnergySaver/AuxiliaryChilledWaterCoolingcanoperatesimultaneouslywithcompressor
cooling. An optional discharge temperature sensor is required.
2.TheEnergySaver/AuxiliaryChilledWaterCoolingwillbethesameandthecompressorrules
for short-cycle time will not be violated.
3. The following is the compressor staging sequence at each adjustment period.
UNITS WITH STANDARD (DUAL) SCROLL COMPRESSORS
Cool 1 ON at Temperature Setpoint + Temperature Deadband + 1.3°F and Valve 100% Open
Cool 2 ON at Temperature Setpoint + Temperature Deadband + 1.6°F and Valve 100% Open
Cool 2 OFF at Temperature Setpoint + 1.6°F and Valve 100% Open
Cool1OFFatTemperatureSetpoint+1.3°FandValve100%Openuntilnextadjustmentperiod
UNITS WITH OPTIONAL TANDEM SCROLL or SEMI-HERMETIC (W/UNLOADING) COMPRESSORS
Cool 1 ON at Temperature Setpoint + Temperature Deadband + 1.3°F and Valve 100% Open
Cool 2 ON at Temperature Setpoint + Temperature Deadband + 1.6°F and Valve 100% Open
Cool 3 ON at Temperature Setpoint + Temperature Deadband + 1.9°F and Valve 100% Open
Cool 4 ON at Temperature Setpoint + Temperature Deadband + 2.2°F and Valve 100% Open