69•dap4UserManual
Cool 4 OFF at Temperature Setpoint + 2.2°F and Valve 100% Open
Cool 3 OFF at Temperature Setpoint + 1.9°F and Valve 100% Open
Cool 2 OFF at Temperature Setpoint + 1.6°F and Valve 100% Open
Cool1OFFatTemperatureSetpoint+1.3°FandValve100%Openuntilnextadjustmentperiod
REHEAT
1. There is a one (1) minute delay between the stop of any reheat stage to the start of any reheat
stage.
2. There is a one (1) minute delay from the start-to-start of different reheat stages. Reheat stages
rotate every 100 hours of runtime.
3. The reheat staging at each adjustment period is as follows:
Reheat 1 ON at Temperature Setpoint – Temperature Deadband
Reheat 2 ON at Temperature Setpoint – Temperature Deadband – y°F
Reheat 3 ON at Temperature Setpoint – Temperature Deadband – 2y°F
Reheat 3 OFF at Temperature Setpoint – 2y°F
Reheat 2 OFF at Temperature Setpoint – y°F
Reheat 1 OFF at Temperature Setpoint
Note: y = “stage to stage” which can be changed in MenuB-Setpoints; default value is 0.3
4. The above reheat staging is for the standard 3 stage electric reheat. Other types of reheat are
available (hot water and hot gas). They are single stage. Single stage operates in the follow-
ing manner:
Reheat is ON at Temperature Setpoint – Temperature Deadband
Reheat is OFF at Temperature Setpoint
5.Reheatwillbeoverriddenbyhumidicationwhenthehumidiersettingisprogrammedfor
Computer, Non-Modulating or Computer, Modulating (See Menu J – Factory Settings).
ELECTRIC REHEAT LOGIC
Menu J - Factory Settings: Reheat Settings
- 1 ELECTRIC (for single stage electric reheat)
This setting will be default on Mini-dap4 panel and optional in dap4 panel.
When panel is programmed to “1 ELECTRIC” the reheat only allows coming on during the
dehumidicationcoolingcycle.Whenreheatcomeson,itwilltrytosatisfytheunittempera-
turesetpoint.Ifthehumiditysetpointsatisesandthedehumidicationcoolingstops,the
reheat will be disable as well.
- 3 ELECTRIC (For three stages electric reheat)
This setting will be optional in dap4 panel.
When panel is programmed to “3 ELECTRIC” the reheat stages only allow coming on during
thedehumidicationcoolingcycle.Whenreheatwillstageonbasesontemperaturesetpoint
and try to satisfy the temperature setpoint. While reheat is demanded, if the humidity
setpointissatisedandthedehumidicationcoolingstops,thereheatstageswillbedisable
as well.