EasyManuals Logo

Data Aire dap 4 User Manual

Data Aire dap 4
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #74 background imageLoading...
Page #74 background image
74•dap4UserManual
Open20%ifreturn_relative_humidity=humidity_setpoint–0.8%
Open30%ifreturn_relative_humidity=humidity_setpoint–0.7%
Open40%ifreturn_relative_humidity=humidity_setpoint–0.6%
Open50%ifreturn_relative_humidity=humidity_setpoint–0.5%
Open60%ifreturn_relative_humidity=humidity_setpoint–0.4%
Open70%ifreturn_relative_humidity=humidity_setpoint–0.3%
Open80%ifreturn_relative_humidity=humidity_setpoint–0.2%
Open90%ifreturn_relative_humidity=humidity_setpoint–0.1%
Open100%ifreturn_relative_humidity=humidity_setpoint
Chilled Water valve closing
Whilestillindehumidicationmode,ChilledWatervalvewillstarttocloseifdewpointisde-
creasing OR relative humidity is decreasing closer to the setpoints minus deadband. The
modulation of the CW valve will be based on whichever has HIGHER demand for CW valve to
open.Forexample,ifdewpointrequirestheCWvalvetoopen20%andhumidityrequiresthe
CW valve to open 50%, as a result, CW valve will open 50%. Individual logic for CW valve
closing based on dewpoint and humidity is as followed:
CW valve modulation based on dewpoint
Starttocloseifreturndewpointdropstohigh_dewpoint_setpoint–high_dewpoint_deadband;
after that, the CW valve will:
Open90%ifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband–0.1°F
Open80%ifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband–0.2°F
Open70%ifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband–0.3°F
Open60%ifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband–0.4°F
Open50%ifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband–0.5°F
Open40%ifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband–0.6°F
Open30%ifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband–0.7°F
Open20%ifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband–0.8°F
Open10%ifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband–0.9°F
Closedifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband-1.0°F
CW valve modulation based on humidity
Startstocloseifreturn_relative_humiditydropstohumidity_setpoint–humidity_deadband;
after that, the CW valve will:
Open90%ifreturn_relative_humidity=humidity_setpoint–humidity_deadband–0.1%
Open80%ifreturn_relative_humidity=humidity_setpoint–humidity_deadband–0.2%
Open70%ifreturn_relative_humidity=humidity_setpoint–humidity_deadband–0.3%
Open60%ifreturn_relative_humidity=humidity_setpoint–humidity_deadband–0.4%
Open50%ifreturn_relative_humidity=humidity_setpoint–humidity_deadband–0.5%
Open40%ifreturn_relative_humidity=humidity_setpoint–humidity_deadband–0.6%
Open30%ifreturn_relative_humidity=humidity_setpoint–humidity_deadband–0.7%
Open20%ifreturn_relative_humidity=humidity_setpoint–humidity_deadband–0.8%
Open10%ifreturn_relative_humidity=humidity_setpoint–humidity_deadband–0.9%
Closedifreturn_relative_humidity=humidity_setpoint–humidity_deadband–1.0%
Humidier Operation
HumidierwillturnonwhendewpointisbelowLowDewpointSetpoint
HumidierwillturnoffwhendewpointisaboveLowDewpointSetpoint+LowDewpointDeadband

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Data Aire dap 4 and is the answer not in the manual?

Data Aire dap 4 Specifications

General IconGeneral
BrandData Aire
Modeldap 4
CategoryControl Unit
LanguageEnglish