74•dap4UserManual
Open20%ifreturn_relative_humidity=humidity_setpoint–0.8%
Open30%ifreturn_relative_humidity=humidity_setpoint–0.7%
Open40%ifreturn_relative_humidity=humidity_setpoint–0.6%
Open50%ifreturn_relative_humidity=humidity_setpoint–0.5%
Open60%ifreturn_relative_humidity=humidity_setpoint–0.4%
Open70%ifreturn_relative_humidity=humidity_setpoint–0.3%
Open80%ifreturn_relative_humidity=humidity_setpoint–0.2%
Open90%ifreturn_relative_humidity=humidity_setpoint–0.1%
Open100%ifreturn_relative_humidity=humidity_setpoint
Chilled Water valve closing
Whilestillindehumidicationmode,ChilledWatervalvewillstarttocloseifdewpointisde-
creasing OR relative humidity is decreasing closer to the setpoints minus deadband. The
modulation of the CW valve will be based on whichever has HIGHER demand for CW valve to
open.Forexample,ifdewpointrequirestheCWvalvetoopen20%andhumidityrequiresthe
CW valve to open 50%, as a result, CW valve will open 50%. Individual logic for CW valve
closing based on dewpoint and humidity is as followed:
CW valve modulation based on dewpoint
Starttocloseifreturndewpointdropstohigh_dewpoint_setpoint–high_dewpoint_deadband;
after that, the CW valve will:
Open90%ifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband–0.1°F
Open80%ifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband–0.2°F
Open70%ifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband–0.3°F
Open60%ifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband–0.4°F
Open50%ifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband–0.5°F
Open40%ifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband–0.6°F
Open30%ifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband–0.7°F
Open20%ifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband–0.8°F
Open10%ifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband–0.9°F
Closedifreturndewpoint=high_dewpoint_setpoint–high_dewpoint_deadband-1.0°F
CW valve modulation based on humidity
Startstocloseifreturn_relative_humiditydropstohumidity_setpoint–humidity_deadband;
after that, the CW valve will:
Open90%ifreturn_relative_humidity=humidity_setpoint–humidity_deadband–0.1%
Open80%ifreturn_relative_humidity=humidity_setpoint–humidity_deadband–0.2%
Open70%ifreturn_relative_humidity=humidity_setpoint–humidity_deadband–0.3%
Open60%ifreturn_relative_humidity=humidity_setpoint–humidity_deadband–0.4%
Open50%ifreturn_relative_humidity=humidity_setpoint–humidity_deadband–0.5%
Open40%ifreturn_relative_humidity=humidity_setpoint–humidity_deadband–0.6%
Open30%ifreturn_relative_humidity=humidity_setpoint–humidity_deadband–0.7%
Open20%ifreturn_relative_humidity=humidity_setpoint–humidity_deadband–0.8%
Open10%ifreturn_relative_humidity=humidity_setpoint–humidity_deadband–0.9%
Closedifreturn_relative_humidity=humidity_setpoint–humidity_deadband–1.0%
Humidier Operation
HumidierwillturnonwhendewpointisbelowLowDewpointSetpoint
HumidierwillturnoffwhendewpointisaboveLowDewpointSetpoint+LowDewpointDeadband