84•dap4UserManual
Dehumidicationcycleson
-- If unit is not in cooling mode, C1 variable speed compressor turns on when humidity
is at Humidity Setpoint + Humidity Deadband then runs at its minimum speed (0V).
C1 compressor will modulate from 0% to 100% in 0.1% RH increment (10% speed
for each 0.1% RH). It will operate at 100% speed when humidity rises to Humidity
setpoint + Humidity deadband+ 1%. For instance:
If Humidity = Humdity SP + Hum Deadband, C1 will run at 0%
If Humidity = Humdity SP + Hum Deadband + 0.1%, C1 will run at 10%
If Humidity = Humdity SP + Hum Deadband + 0.2%, C1 will run at 20% Etc.
-- C2xedspeedcompressorcyclesonatHumiditysetpoint+Humiditydead
band+1.1%.
-- If space is overcool, reheat will come on based on temperature setpoint and C2
compressor will turn off. C1 variable speed compressor will continue to run
untilhumiditysetpointsatisesbutnottoviolatethedehumidicationinhibitlogic
(In limit/ No limit) stated above.
-- Ifunitisincoolingmodeanddehumidicationmodeissetto“1Cinlimit”or“2Cin
limit”,thetemperaturecoolingcontrolmodewilloverridethedehumidicationcontrol
(cooling control will follow the temperature setpoint). Otherwise, dap4 will continue to
nishthedehumidicationcyclethenreversetotemperaturecontrolcoolingmode.
Dehumidicationcyclesoff
-- Whenhumiditydrops,FixedspeedcompressorC2(NO3)willturnoffwhenhumidity
= Humidity Setpoint +1%.
-- C1willrampuptomaximumspeedforamodulationdelayperiodwhenC2turnsoff.
-- Variable speed compressor C1 starts to ramp down in 0.1 % RH decrement when
Humidity drops to Humdity Setpoint + 1% (decreasing 10% speed for every
0.1%RH).
-- C1 compressor will run at its minimum speed when humidity = Humidity SP.
-- Compressor C1 turns off (NO2 signal off) when humidity = Humidity SP - 1% and
compressorminimumruntimehasexpired.
B. Dewpoint control mode
ThehumidiercontrolmodeissettoDewpoint.Highdewpointsetpoint,lowdewpointsetpoint
and dewpoint deadbands are programmed on dap4- menu B - Setpoint.
a) Single Variable speed compressor system
Dehumidicationcycleson-Dewpointtemperatureisrising
-- If unit is not in cooling mode, the variable speed compressor turns on when
dewpoint is at High dewpoint SP- 1Deg F and operates at minimum speed (0V) then
it will modulate from 0% to 100% in 0.1% increment if dewpoint rises to high
dewpoint setpoint. For instance:
If dewpoint = High dewpoint SP – 1 Deg F, compressor will run at 0% (0VDC)
If dewpoint = High dewpoint SP – 0.9 DegF, compressor will run at 10% (1V)
If If dewpoint = High dewpoint SP – 0.8 DegF, compressor will run at 20% (2V) Etc.