83•dap4UserManual
e) Ifdehumidicationisprogrammedfor“1Cinlimit”or“2Cinlimit”thedehumidication
cooling will be inhibited by reheat if the return air temperature drops below Temperature
Setpoint-TemperatureDB-2degF.Dehumidicationwillbeinhibiteduntilthereturnair
temperature rises above the Temperature Setpoint. Compressor short-cycle time will not
be violated.
f) Ifdehumidicationisprogrammedfor“1CNoLimit”or“2CNoLimit”,dehumidication
remainsonuntilthehumiditysetpointisreached.Inthismode,dehumidicationhas
priority and overcooling is disregarded. The reheat sequence will remain the same.
g) Thereisaone(1)minutedelaybetweenstop-to-startofdehumidicationcooling.
Compressor short-cycle time delay will not be violated.
h) Thereisave(5)minutedelaybetweendehumidicationandhumidication.
i) Relative humidity control mode is not recommended for discharge temperature control,
Dewpoint control method should be used in this case.
j) Thecompressorstagingsequencefordehumidicationcoolingisasfollows:
A. Relative humidity control mode:
a) Single Variable speed compressor system
Dehumidicationcycleson
-- If unit is not in cooling mode, the variable speed compressor turns on when humidity
is at Humidity Setpoint (HSP) + Humidity Deadband (HDB).
Compressor will modulate its speed from 0% to 100% in 1%RH above Humidity
Setpoint +Humidity DB. For instance:
If Humidity = Humdity Setpoint + Hum Deadband, VFD will run at 0VDC
If Humidity = Humdity Setpoint + Hum Deadband + 0.1%, VFD will run at 10%
If Humidity = Humdity Setpoint + Hum Deadband + 0.2%, VFD will run at 20% Etc.
-- Ifcoolingrequiresduringdehumidicationcycleanddehumidicationmodeisset
to“1Cinlimit”thetemperaturecoolingcontrolwilloverridethedehumidication
coolingcontrol.Ifdehumidicationmodeissetto“1CNolimit”,unitwillcontinueto
nishthedehumidicationcyclethenswitchtotemperaturecontrolcoolingmode.
Dehumidicationcyclesoff
-- Variable speed compressor C1 starts to ramp down in 0.1 % RH decrement when
Humidity drops to Humdity Setpoint + 1%. Compressor decreases 10% speed for
each 0.1%RH.
-- When Humidity equals Humdity Setpoint, compressor runs at its minimum speed
(0 VDC).
-- When Humidity is at Humidity Setpoint – 0.5 % and compressor minimum runtime
expired,compressorturnsoff(NO2startsignalturnsoff).
b) DualDXcircuitwithavariablespeedcompressorandaxedspeedcompressor

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Data Aire dap 4 and is the answer not in the manual?

Data Aire dap 4 Specifications

General IconGeneral
BrandData Aire
Modeldap 4
CategoryControl Unit
LanguageEnglish