85•dap4UserManual
-- Ifunitisincoolingmodeduringdehumidicationcycleanddehumidicationmode
is set to “1C in limit”, the cooling control (By temperature setpoint) will override the
dewpointcontrol.Ifdehumidicationmodeissetto“1CNoLimit”,unitwillcontinue
tonishthedewpointcontrolcyclethenreversetothecoolingcontrol.
Dehumidicationcyclesoff-Dewpointisdropping
-- Variable speed compressor C1 starts to ramp down in 0.1 % decrement when
dewpoint drops to high dewpoint Setpoint – high dewpoint deadband.
-- Compressor will run at minimum speed (0V) when dewpoint is at high dewpoint
setpoint – high dewpoint deadband-1°F.
-- Compressor turns off (NO2 start signal turns off) when dewpoint equals to high
dewpoint setpoint – high dewpoint deadband-1.5 deg F and compressor minimum
runtimehasexpired.
b) DualDXcircuitwithavariablespeedcompressorandaxedspeedcompressor
Dehumidicationcycleson–dewpointisrising
-- If unit is not in cooling mode, If dewpoint continues to rise, the variable speed
compressor will turns on when dewpoint = High dewpoint SP- 1Deg F and operates
at minimum speed (0V) then modulates from 0% to 100% in 0.1% increment if
dewpoint rises to high dewpoint setpoint. For instance:
If dewpoint = High dewpoint SP – 1 Deg F, compressor will run at 0% (0VDC)
If dewpoint = High dewpoint SP – 0.9 DegF, compressor will run at 10% (1V)
If If dewpoint = High dewpoint SP – 0.8 DegF, compressor will run at 20% (2V) Etc.
-- C2xedspeedcompressorwillcycleonwhendewpoint=highdewpointsetpoint.
-- If space is overcool, reheat will come on based on temperature setpoint and C2
compressor will turn off. C1 variable speed compressor will continue to operate until
dewpoint drops below High dew setpoint – High DP DB-1 Deg F but not to violate
thedehumidicationinhibitlogic(Inlimit/Nolimit)statedabove.
-- Ifcoolingisonduringdehumidicationcycleanddehumidicationmodeissetto“2C
in limit” or “1C in limit”, the temperature cooling control will override the dewpoint
control.Ifdehumidicationmodeissetto“1CNoLimit”or“2CNoLimit”theunitwill
continuetonishthedewpointcontrolcyclethenreversetothetemperaturecontrol.
Dehumidicationcyclesoff-dewpointisdropping
-- C2xedspeedcompressor(NO3)willturnoffwhendewpoint=Highdewpoint
Setpoint – highdewpoint deadband.
-- Variable speed compressor C1 starts to ramp down in 0.1 % decrement when
dewpoint drops below High dewpoint Setpoint – High dewpoint deadband.
-- C1 compressor will run at minimum speed when dewpoint = High dewpoint SP-
dewpoint deadband-1°F.
-- C1 compressor turn off (NO2) when dewpoint = High dewpoint SP –dewpoint
deadband - 1.5 Deg F and variable speed compressor minimum runtime has
expired.