EasyManuals Logo

Data Aire dap 4 User Manual

Data Aire dap 4
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #40 background imageLoading...
Page #40 background image
40•dap4UserManual
Available Selections:
Comp Short Cycle: Yes or No
Water Alarm Action: Alarm Only
Shutdown Unit
Lockout Comps
Reset Alarm Log: Yes or No
Alarm Screen Contact: No Contact Message
Service Company
Maint Engineer
Data Proc Mngr
Custom Message (factory installed)
Once a selection or selections have been made, move the cursor to the title block by pressing the
ENTER key
▼PresstheDOWNkeytoviewthenextscreen:
The following will be displayed (values are for reference only):
Available Selections:
No Water Flow Action: Alarm Only
Turn Compressors Off
Wtr Flow Alm Dly: The range is 5 to 180 seconds
Air Flow Alm Dly: The range is 5 to 180 seconds
Once a selection or selections have been made, move the cursor to the title block by pressing the
ENTER key
Flow Alarm
No Water Flow Action:
Alarm Only
Wtr Flow Alm Dly: 5s
Air Flow Alm Dly: 5s

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Data Aire dap 4 and is the answer not in the manual?

Data Aire dap 4 Specifications

General IconGeneral
BrandData Aire
Modeldap 4
CategoryControl Unit
LanguageEnglish