40•dap4UserManual
Available Selections:
Comp Short Cycle: Yes or No
Water Alarm Action: Alarm Only
Shutdown Unit
Lockout Comps
Reset Alarm Log: Yes or No
Alarm Screen Contact: No Contact Message
Service Company
Maint Engineer
Data Proc Mngr
Custom Message (factory installed)
Once a selection or selections have been made, move the cursor to the title block by pressing the
ENTER key
▼PresstheDOWNkeytoviewthenextscreen:
The following will be displayed (values are for reference only):
Available Selections:
No Water Flow Action: Alarm Only
Turn Compressors Off
Wtr Flow Alm Dly: The range is 5 to 180 seconds
Air Flow Alm Dly: The range is 5 to 180 seconds
Once a selection or selections have been made, move the cursor to the title block by pressing the
ENTER key
Flow Alarm
No Water Flow Action:
Alarm Only
Wtr Flow Alm Dly: 5s
Air Flow Alm Dly: 5s