EasyManuals Logo

Data Aire dap 4 User Manual

Data Aire dap 4
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #77 background imageLoading...
Page #77 background image
77•dap4UserManual
For instance: SP = 72, DB = 2, STS = 0.3. Compressor will be on at 74.3 deg.
Return air temperature is dropping (Off cycle):
-- FixedspeedcompressorC2turnsoffwhenreturnairtemperaturedropsbelow
temperature setpoint – STS band (default STS band=0.3 deg F) for duration of C2
off delay (default =5s). For instance: SP = 72, STS = 0.3 Compressor goes off at
71.7 degrees after 5 seconds delay.
-- AfterFixedspeedcompressorC2turnsoff,variablespeedcompressorC1ramps
uptoitsmaximumspeedandoperatesatmaximumspeedfora“DelayModulation”
period (default=60s). The Delay modulation is set in the Compressor/Factory
settings menu.
-- Variable speed compressor C1 will then modulate to maintain setpoint and turns
off when return air temperature drops to temperature setpoint – C1offset
(default=2degF); and C1 has operated for at least minimum runtime period.
For instance: SP= 72, C1 offset = 2, compressor goes off at 70 deg if it has ran for
6 minutes (minimum runtime is set to 6 minutes).
c) Energysaver/auxiliarycoolingwithoutDXcoolingassist.
1. EnergySaver/AuxiliaryChilledWaterCoolingwillbeavailablewheneverthe
incoming water supply is below the setpoint of the Energy saver Water Thermostat
in menu B-setpoint – Energy Saver
2. TheEnergySaver/AuxiliaryChilledWatermodewilloperatewhenspace
temperature is between the return air setpoint plus deadband and plus Energy
saver to DX change-over band. If the temperature rises above this range, Energy
Saver/AuxiliaryChilledWaterCoolingwillbeinhibitedforatleast15minutetoan
hour (see Energy saver Lockout setting in Factory settings menu for details) and
only DX cooling will be available. After a lockout time delay, system will try Energy
Saver/AuxiliaryChilledWaterCoolingagain.
3. The chilled water valve proportionally opens 10% for each 0.1ºF above the
temperature setpoint + temperature deadband.
4. If the temperature is consistently rising, then the valve will be opened wider.
Likewise, if the temperature is consistently falling, then the valve will be close
gradually. However, if temperature movement changes directions, then it must
change the amount of the deadband before the valve will be repositioned.
The temperature can be slowly drifting back and forth within a deadband window
at any point in the adjustment period and no valve position changes will be made.
5. If the current temperature is higher than temperature setpoint, the following
sequence is used to determine the new valve position.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Data Aire dap 4 and is the answer not in the manual?

Data Aire dap 4 Specifications

General IconGeneral
BrandData Aire
Modeldap 4
CategoryControl Unit
LanguageEnglish