-- If variable speed compressor C1 runs at the minimum speed for a period of time,
itwillautomaticallyrampuptothemaximumspeedforoneminutetomaintain
the minimum compressor oil level. The temperature may drop slightly during this
override period.
-- Compressor cycles on and modulate as follows:
Discharge air temperature is rising (On cycle):
-- When discharge air temperature rises to temperature setpoint + temperature DB
(deadband), variable speed compressor C1 will start and operate at its minimum
speed.
-- Dap4 will then use PID (proportional-Integral- derivative) control logic to modulate
the variable speed compressor C1 to maintain temperature setpoint. PID values are
programmed in Factory settings menu.
Discharge air temperature is dropping (Off cycle):
-- Compressor C1 turns off when discharge air temperature drops to temperature
setpoint – C1 offset. C1 offset is programmed in Compressor /Factory settings
menu.
-- CompressorC1canonlyturnoffifminimumruntimehasexpired.
b) DualDXcircuit:Combinationofavariablespeedcompressor(C1)andaxedspeed
compressor (C2) system
-- Compressor settings type in dap4 Factory Settings menu is programmed to
“Vari+Fixed”andControlmodeissetto“Supply”.
-- Thereisave(5)minutedelaybetweenstart-to-startofthesameprimarystage.
Thedelaywillbeincreasedtosix(6)minutesforone(1)hourfollowingthedetection
of a short-cycle condition even if the short cycle alarm is disabled using a short cycle
alarm menu.
-- There is a two (2) minute delay between stop-to-start of the same compressor.
-- There is minimum two (2) minutes delay between the start of variable speed
compressorandstartofxedspeedcompressor.
-- Once variable speed compressor C1 comes on, it must remain on for a minimum
runtimeevensetpointsatises.
-- Compressor cycles on and modulate as follows:
Discharge air temperature is rising (On cycle):
-- When discharge air temperature rises to temperature setpoint + 0.5 temperature
deadband (SP+1/2 DB), variable speed compressor C1will start.
-- Dap4 will then use PID (proportional- Integral- derivative) logic to control the
compressor C1 speed to maintain temperature setpoint.
-- FixedspeedcompressorC2willcomeonwhendischargeairtemperaturerises
to temperature setpoint + temperature deadband (SP+DB) and compressor C1 has
operatedatabove95%ofitsmaximumspeedforatleastC2ondelay.C2ondelay
is programmed in Compressor/Factory settings menu.