gForce Ultra IOM
100
Manually Open and Close the EEV
Follow the previous screens to the Regulation Menu screen.
Change “Enable manual valve position” from 0 to 1 and “Manual valve position from 0stp to a desired
step value. There are 480 steps total for the EEV. So, if you would like the valve to open 62.5%, enter
“300stp” such as below.
Once all the changes are done, press ESC to return to the Main screen and verify the valve opening
position.
Do not forget to revert the control back to automatic by changing the “Enable manual valve position”
back to 0 from 1.