gForce Ultra IOM
96
Electronic Expansion Valve Drive (EDV)
Setup Using Display Panel Guide
EVD Display Panel enables viewing and changing of critical system info:
Values which can be viewed only:
- Suction Temperature
- Electronic Expansion Valve pressure
- Superheat
Values that may be changed:
- Superheat set-point
- Manual opening/closing of Electronic Expansion Valve (EEV) to a fixed position
The suction temperature, suction pressure and super heat values can be viewed on our dap4 display.
The dap4 reads this information from the Electronic Valve Driver (EVD) and allows the user to view the
following system information via Menu D: Input/Output.
This guide is not intended to be used as a means of altering the values which are set at the factory. Any
changes made must be first discussed with a Data Aire trained technician.
Figure 22 Typical EVD Display View
To change or view Configurations, press the PRG key, and enter password “0066”.