dap4 Settings for Ultra Units
Optional Sensor #2: Choose Name: Enable:
Channel:
Normal:
Minimum:
Maximum:
Offset:
Value:
Off (Default)
U03 (Default)
4-20mA (Default)
0.0 (Default)
1000 (Default)
0.0F (Default)
0.0F (Reading, not a setting)
Optional Sensor #3: Hot Gas Temp: Enable:
Channel:
Normal:
Minimum:
Maximum:
Offset:
Value:
On
U06 (Default)
PT1000
0.0 (Default)
100.0 (Default)
0.0F (Default)
0.0F (Reading, not a setting)
Optional Sensor #4: Choose Name: Enable:
Channel:
Normal:
Offset:
Value:
Off (Default)
U08 (Default)
NTC (Default)
0.0F (Default)
0.0F (Reading, not a setting)
Optional Sensor #5: Cond Sup Temp: Enable:
Channel:
pCOe Module:
Offset:
Value:
Off (Default)
B2 (Default)
NTC (Default)
0.0F (Default)
0.0F (Reading, not a setting)
Analog Output Config: Optional Output #2
Channel:
Action:
Minimum:
Maximum:
NOTE: Variable speed compressor limit
Y5 (Default)
DIRECT (Default)
2.00 VDC
8.50 VDC
Analog Output Config: Fan Speed: Channel:
Action:
Minimum:
Maximum:
Y3
Direct
0.00vdc
10.00vdc
I/O Module: Liq Line Temp:
Value:
Liq Line Prs:
Value:
Minimum:
Maximum:
Not Used
32.0F
Not Used
0 psi
0 psi
650 psi
I/O Module: Discharge Pressur:
Value:
Minimum:
Maximum:
Enabled
Displays actual reading
0psi
650psi