Condensate pumps which ship loose, normally require a separate source of power. Always check the
pump power requirements before connecting power. Condensate pumps are available in various
voltages.
Factory installed condensate pumps are wired to display a ā€œHigh Condensate Water Levelā€ alarm. The
wiring for this must be done in the field on pumps that ship loose.
Condensate Probe
One (1) condensate probe for sensing water under the floor is standard and is included with this unit.
This comes in a plastic bag with about 15 feet (4.6 m) of coiled-up wire. The condensate probe is a
rectangular box that is typically placed below the unit in a location where the water is likely to
accumulate. Additional probes are available as an option.
Place the probe flat on the floor on top of a thin layer of non-conductive silicone. Secure the attached
wires where necessary. A longer length of standard hookup wire may be used if required.
WARNING: Failure to remove the condensate probe from the plastic bag
and uncoil the length of wire attached to the probe will leave the unit
unprotected for sensing water under the unit and can result in a nuisance
water detected alarm. Remove/disconnect the probe if it is not to be used.
Water Sensing Cable (Optional)
Some units may be equipped with an optional water detection cable in addition to or in lieu of the
condensate probe. The cable can sense moisture anywhere along its length. It is typically placed below
the unit in a rectangular pattern that matches the perimeter of the unit. The cable is connected to the
terminal board and ready for installation. Cable lengths will vary depending on the original order and
specifications. Care should be taken when installing the cable. Be sure the cable is not touching metal
and/or any debris under the raised floor.
Remote Temperature and Humidity Sensors (Optional)
Although existing unit mounted sensors can be removed for remote mounting, the remote sensor option
provides a more convenient means of field installation. This is because the sensors are already
connected to a predetermined length of cable and come mounted in a remote sensor enclosure. The
temperature and humidity sensors require a total of five wires and should be twisted, shielded cable
type.
When ordered, the remote sensors are shipped with 35 feet (11 m) standard length or 50 feet (15 m)
to 100 feet (30.5 m) optional length of cable and comes mounted in a decorative wall mounted
enclosure.