Ethernet Communication Module IFD9506
DVP-PLC Operation Manual
22
1. Bit Device:
Provides bit-device addresses of serial slaves; able to read the content in the corresponding addresses of
the designated slave.
Station Address: Enter the slave address of the Modbus device to which IFD9506 connects.
Modbus (Hex): Enter the absolute address of the slave in 4 hexadecimal digits. For example, the
address of M0 in the Delta PLC is 0x0800.
Modbus (Dec): Enter the absolute address of the slave in 6 decimal digits. For example, the address
of M0 in the Delta PLC is 002049.
Amount: The number of devices starting from the entered Modbus address to be read
2. Word Device:
Provides word-device addresses of serial slaves; able to read the content in the corresponding address of
the designated slave. The operation of word devices is the same as bit devices.