Chapter 9  Serial Communication Module AS00SCM 
9- 65 
 
9.6.3 Remote IO Application (AS-FCOPM)   
This example shows other series PLC, AH10COPM-5A, as a CANopen Master that controls four IO modules on the 
right side of AS00SCM-A that acts as a CANopen Slave. (You can use this method to connect to a 3
rd
 party PLC.) 
AS300 
Scan and download AS00SCM-A (RTU mode),   
right side module configurations 
AHCPU530-EN + AH10COPM-5A 
4 Analog channels for output 
AS04AD-A  4 Analog channels for input 
 
Step 1 
Use AS300 to connect to AS00SCM-A through AS Remote Communication (RTU mode) and then use HWCONFIG to 
scan and download the parameters. If the Card 2 LED is blinking normally, with no error messages, and no need to 
download the PLC programs, the device power can be turned off. Refer to Section 9.4.1.1 for reference.