Chapter 11  DeviceNet  Master Scanner  Module  AS01DNET-A 
11-95 
1
  80 means AS01DNET (RTU) is in STOP state. 
  02 is the node ID: 2 of AS01DNET (RTU). 
 
11.5.6.3.  Status Word Diagnosis 
 
The status word of AS01DNET (RTU) shows the operation states of special modules and digital I/O modules. See the 
following table for status word diagnosis and disposal. 
 
Bit 
Status 
Description  Disposal 
bit0 
AS01DNET (RTU) is in RUN state   
AS01DNET (RTU) is in STOP state. 
bit1 
0 
Valid configuration data  in 
No correction needed 
1 
Invalid configuration data  in  AS01DNET 
(RTU) 
Re-
download the configuration data to 
AS01DNET  (RTU)  by using the DeviceNet 
Builder software. 
Reserved  ——  —— 
bit4 
0 
Currently connected module matches the 
configuration in the software. 
No correction needed 
1 
Currently connected module is 
inconsistent with the configuration in the 
software. 
1.  Check if currently connected 
module is 
consistent with the configuration in the 
software. 
2. 
Change current module to match the 
configuration in the software or change the 
configuration in the software to match 
currently connected module. 
bit5 
AS01DNET(RTU) in normal operation 
1  AS01DNET(RTU) in low voltage 
Check if the power supply for AS01DNET (RTU) 
bit7 
AS01DNET(RTU) in normal operation 
 
 
Reserved  ——  —— 
Reserved  ——  ——