Chapter  10  Function Cards 
10-53 
10.4  Wiring 
10.4.1  AS-F2AD   
 
Shielded cable *1
Shielded cable *1
2-wi re: c urre nt i nput
3-wire: v oltage in put
Shielded cable *1
Shielded cable *1
3-wire: c urrent i np ut
 
 
*1. Use shielded cables to isolate the analog input signal cable from other power cables. 
*2. If the module is connected to a current signal, the terminals Vn and In+ (n=1–2) must be short-circuited. 
*3. If variability in the input voltage results in interference within the wiring, connect the module to a capacitor having a 
capacitance in the range of 0.1–0.47 μF and a working voltage of 25 V. 
*4. Connect the shielded cable to the terminal FE. 
*5. The wording “CHX” indicates that you can use the five wiring methods listed above for every input channel.