AS Series Module Manual 
4- 12 
5.  Scale Range 
You can set the scale range when the format is floating-point. The analog output mode of a channel has a 
corresponding digital range. Digital values correspond to analog outputs sent by the module. For example, if 
the analog range is -10 V to +10 V, the digital range is -10.0 to +10.0, the HSP scale is 10.0, and the LSP 
scale is -10.0. The digital values -10.0 to +10.0 correspond to the analog values -10 V to +10 V, as the 
example below shows.   
 
 
 
 
 
 
4.2.6  Wiring 
  Precautions 
To ensure the digital-to-analog module functions well and reliably, the external wiring must prevent noise. 
(1)  To prevent a surge and induction, the AC cable and the output signal cables that are connected to the 
AS04DA-A must be separate cables. 
(2)  Do not install or bound the cable to a main circuit, a high-voltage cable, or a cable connected to a 
load that is not a PLC. 
(3)  Ground shielded cables and hermetically sealed cables separately. 
(4)  Terminals with insulation sleeves cannot be arranged as a terminal block, so you should cover the 
terminals with insulation tubes. 
(5)  Connect 24 to 22 AWG (1 mm) wires to the input/output terminals. The plastic jackets that are 
removed from the cables should be 8 mm to 10 mm long. The specifications for the terminals and the 
wiring of the terminals are shown below. Use only copper leads that can resist temperatures above 
60° C /75° C. 
 
(6)  Note: use cables with the same length (less than 200 m) and use wire resistance of less than 100 
ohm.