ASDA-B2-F Control Mode of Operation
September, 2015 6-19
6
bigger than 0. If it is, it means the frequency points in P2-43 and P2-45 are the ones found by
auto resonance suppression. If the value is 0, it means the value of 1000 in P2-43 and P2-45 are
default values which are not the ones found by auto resonance suppression. Deepen the
attenuation rate of the non-existed frequency point might worsen the situation.
Settings of P2-47
Current Value Desired Value Function
0 1
Clear the setting value of P2-43 ~ P2-46 and enable the
function of auto resonance suppression.
0 2
Clear the setting value of P2-43 ~ P2-46 and enable the
function of auto resonance suppression.
1 0
Save the setting value of P2-43 ~ P2-46 and disable the
function of auto resonance suppression.
1 1
Clear the setting value of P2-43 ~ P2-46 and enable the
function of auto resonance suppression.
1 2
Do not clear the setting value of P2-43 ~ P2-46 and enable the
function of auto resonance suppression continuously.
2 0
Save the setting value of P2-43 ~ P2-46 and disable the
function of auto resonance suppression.
2 1
Clear the setting value of P2-43 ~ P2-46 and enable the
function of auto resonance suppression.
2 2
Do not clear the setting value of P2-43 ~ P2-46 and enable the
function of auto resonance suppression continuously.